Parameter Descriptions

9-65 Profile Number

Range:
Function:
0
[0 - 0 ] This parameter contains the profile identification.
*
Byte 1 contains the profile number and byte 2 the
version number of the profile.
NOTE!
This parameter is not visible via LCP.
9-67 Control Word 1
Range:
Function:
0
[0 - 65535 ] This parameter accepts the control word from
*
a Master Class 2 in the same format as PCD 1.
9-68 Status Word 1
Range:
Function:
0
[0 - 65535 ] This parameter delivers the status word for a
*
Master Class 2 in the same format as PCD 2.
9-70 Programming Set-up
Option:
Function:
Select the set-up to be edited.
[0]
Factory setup Uses default data. This option can be used
as a data source to return the other set-ups
to a known state.
[1]
Set-up 1
Edits Set-up 1.
[2]
Set-up 2
Edits Set-up 2.
[3]
Set-up 3
Edits Set-up 3.
[4]
Set-up 4
Edits Set-up 4.
[9]
Active Set-up Follows the active set-up selected in
*
0-10 Active Set-up.
This parameter is unique to LCP and serial communication
busses. See also 0-11 Programming Set-up.

9-71 Profibus Save Data Values

Option:
Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory.
Use this parameter to activate a function that
stores parameter values in the EEPROM non-
volatile memory, so changed parameter values
will be retained at power-down.
[0]
Off
Deactivates the non-volatile storage function.
*
[1]
Store all
Stores all parameter values for all set-ups in the
setups
non-volatile memory. The selection returns to
Off [0] when all parameter values have been
stored.
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
9-71 Profibus Save Data Values
Option:
[2]

9-72 ProfibusDriveReset

Option:
[0]
[1]
[3]
9-75 DO Identification
Range:
0

9-80 Defined Parameters (1)

Array [116]
No LCP access
Read only
Range:
0
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
Range:
0
9-82 Defined Parameters (3)
Array [116]
No LCP access
Read only
Range:
0
®
MG33MD22 - VLT
is a registered Danfoss trademark
Function:
Store all
Stores all parameter values for all set-ups in the
setups
non-volatile memory. The selection returns to
Off [0] when all parameter values have been
stored.
Function:
No action
*
Power-on
Resets Adjustable frequency drive upon
reset
power-up, as for power-cycle.
Comm
Resets the Profibus option only, useful after
option reset
changing certain settings in parameter
group 9-**, e.g., 9-18 Node Address.
When reset, the Adjustable frequency drive
disappears from the serial communication
bus, which may cause a communication
error from the master.
Function:
[0 - 65535 ] Provides information about the DO (Drive
*
Object).
Function:
[0 - 9999 ] This parameter displays a list of all the defined
*
Adjustable frequency drive parameters available
for Profibus.
Function:
[0 - 9999 ] This parameter displays a list of all the defined
*
Adjustable frequency drive parameters available
for Profibus.
Function:
[0 - 9999 ] This parameter displays a list of all the defined
*
Adjustable frequency drive parameters available
for Profibus.
3
3
3-99