Parameter Descriptions
13-01 Start Event
Option:
Function:
[4]
On reference
On reference [4] The motor is running
on reference.
[5]
Torque limit
Torque limit [5] The torque limit, set in
4-16 Torque Limit Motor Mode or
4-17 Torque Limit Generator Mode, has
been exceeded.
[6]
Current limit
Current limit [6] The motor current
limit, set in 4-18 Current Limit, has been
exceeded.
[7]
Out of current
Out of current range [7] The motor
range
current is outside the range set in
4-18 Current Limit.
[8]
Below I low
Below I low [8] The motor current is
lower than set in 4-50 Warning Current
Low.
[9]
Above I high
Above I high [9] The motor current is
higher than set in 4-51 Warning Current
High.
[10]
Out of speed
Out of speed range [10] The speed is
range
outside the range set in 4-52 Warning
Speed Low and 4-53 Warning Speed
High.
[11]
Below speed low
Below speed low [11] The output speed
is lower than the setting in
4-52 Warning Speed Low.
[12]
Above speed
Above speed high [12] The output
high
speed is higher than the setting in
4-53 Warning Speed High.
[13]
Out of feedb.
Out of feedb. Range [13] The feedback
range
is outside the range set in
4-56 Warning Feedback Low and
4-57 Warning Feedback High.
[14]
Below feedb. low
Below feedb. Low [14] The feedback is
below the limit set in 4-56 Warning
Feedback Low.
[15]
Above feedb.
Above feedb. High [15] The feedback is
high
above the limit set in 4-57 Warning
Feedback High.
[16]
Thermal warning
Thermal warning [16] The thermal
warning turns on when the
temperature exceeds the limit in the
motor, the Adjustable frequency drive,
the brake resistor or the thermistor.
[17]
Mains out of
Mains out of range [17] The AC line
range
voltage is outside the specified voltage
range.
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
[18]
[19]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
[27]
[28]
[29]
[33]
[34]
[35]
[36]
[37]
[38]
[39]
[40]
[41]
®
MG33MD22 - VLT
is a registered Danfoss trademark
13-01 Start Event
Option:
Function:
Reversing
Reverse [18] The output is high when
the Adjustable frequency drive is
running counter clockwise (the logical
product of the status bits "running"
AND "reverse").
Warning
Warning [19] A warning is active.
Alarm (trip)
Alarm (trip) [20] A (trip) alarm is active.
Alarm (trip lock)
Alarm (trip lock) [21] A (Trip lock) alarm
is active.
Comparator 0
Comparator 0 [22] Use the result of
comparator 0.
Comparator 1
Comparator 1 [23] Use the result of
comparator 1.
Comparator 2
Comparator 2 [24] Use the result of
comparator 2.
Comparator 3
Comparator 3 [25] Use the result of
comparator 3.
Logic rule 0
Logic rule 0 [26] Use the result of logic
rule 0.
Logic rule 1
Logic rule 1 [27] Use the result of logic
rule 1.
Logic rule 2
Logic rule 2 [28] Use the result of logic
rule 2.
Logic rule 3
Logic rule 3 [29] Use the result of logic
rule 3.
Digital input DI18 Digital input DI18 [33] Use the result of
digital input 18.
Digital input DI19 Digital input DI19 [34] Use the result of
digital input 19.
Digital input DI27 Digital input DI27 [35] Use the result of
digital input 27.
Digital input DI29 Digital input DI27 [35] Use the result of
digital input 29.
Digital input DI32 Digital input DI32 [37] Use the result of
digital input 32.
Digital input DI33 Digital input DI33 [38] Use the result of
digital input 33.
Start command
Start command [39] A start command is
issued.
Drive stopped
Drive stopped [40] A stop command
(Jog, Stop, Qstop, Coast) is issued –
and not from the SLC itself.
Reset Trip
Reset Trip [41] A reset is issued