Parameter Descriptions
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
3
3
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option:
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[84]
SL digital output E
[85]
SL digital output F
[120] Local ref active
3-62
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
See parameter group 13-4*(Smart
Logic Control). If Logic Rule 5 in SLC
is TRUE, the output will go high.
Otherwise, it will be low.
See 13-52 SL Controller Action. Output
A is low on Smart Logic Action [32].
Output A is high on Smart Logic
Action [38].
See 13-52 SL Controller Action. Output
B is low on Smart Logic Action [33].
Output B is high on Smart Logic
Action [39].
See 13-52 SL Controller Action. Output
C is low on Smart Logic Action [34].
Output C is high on Smart Logic
Action [40].
See 13-52 SL Controller Action. Output
D is low on Smart Logic Action [35].
Output D is high on Smart Logic
Action [41]
See 13-52 SL Controller Action. Output
E is low on Smart Logic Action [36].
Output E is high on Smart Logic
Action [42].
See 13-52 SL Controller Action. Output
F is low on Smart Logic Action [37].
Output F is high on Smart Logic
Action [43].
Output is high when 3-13 Reference
Site = [2] Local or when
3-13 Reference Site = [0] Linked to
hand auto at the same time as the
LCP is in [Hand on] mode.
MG33MD22 - VLT
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option:
[121] Remote ref active
[122] No alarm
[123] Start command
activ
[124] Running reverse
[125] Drive in hand mode Output is high when the Adjustable
[126] Drive in auto mode
®
is a registered Danfoss trademark
Function:
Reference site
Local
Remote
set in
referen
reference
3-13 Reference
ce
active
Site
active
[121]
[120]
Reference site:
1
0
Local
3-13 Reference
Site [2]
Reference site:
0
1
Remote
3-13 Reference
Site [1]
Reference site:
Linked to Hand/
Auto
Hand
1
0
Hand -> off
1
0
Auto -> off
0
0
Auto
0
1
Output is high when 3-13 Reference
Site = Remote [1] or Linked to hand/
auto [0] while the LCP is in [Auto on]
mode. See above.
Output is high when no alarm is
present.
Output is high when the Start
command high (i.e., via digital input,
bus connection or [Hand on] or
[Auto on]), and a Stop has been last
command.
Output is high when the Adjustable
frequency drive is running counter
clockwise (the logical product of the
status bits 'running' AND 'reverse').
frequency drive is in [Hand on]
mode (as indicated by the LED
above [Hand on]).
Output is high when the Adjustable
frequency drive is in 'Auto' mode (as
indicated by LED on above [Auto
on]).