Parameter Descriptions
8-08 Readout Filtering
The function is used if the speed feedback value readouts on
serial communication bus are fluctuating. Select filtered if the
function is required. A power-cycle is required for changes to
3
3
take effect.
Option:

3.10.2 8-1* Ctrl. Word Settings

8-10 Control Word Profile

Select the interpretation of the control and status words
corresponding to the installed Serial communication bus. Only
the selections valid for the Serial communication bus installed in
slot A will be visible in the LCP display.
For guidelines in selection of FC profile [0] and PROFIdrive profile
[1] please refer to the Serial communication via RS 485 Interface
section.
For additional guidelines in the selection of PROFIdrive profile [1],
ODVA [5] and CANopen DSP 402 [7], please refer to the
Instruction Manual for the installed Serial communication bus.
Option:
[0]
*
[1]
[5]
[7]
[8]

8-13 Configurable Status Word STW

Option:
[0]
No function
[1]
Profile Default
*
[2]
Alarm 68 Only
[3]
Trip excl Alarm
68
[10] T18 DI status
[11] T19 DI status
3-86
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
16-12 Motor Voltage
16-14 Motor Current
16-16 Torque [Nm]
16-17 Speed [RPM]
16-22 Torque [%]
16-25 Torque [Nm] High
Function:
FC profile
PROFIdrive profile
ODVA
CANopen DSP 402
MCO
Function:
The input is always low.
Depended on the profile set in
8-10 Control Profile.
The input will go high whenever Alarm 68
is active and will go low whenever no
alarm 68 is active
The input will go high whenever Trip on
other alarms is active, and then Alarm 68
is active.
The input will go high whenever T18 has
24 V and will go low whenever T18 has 0
V.
The input will go high whenever T19 has
24 V and will go low whenever T19 has 0
V.
MG33MD22 - VLT
8-13 Configurable Status Word STW
Option:
[12] T27 DI status
[13] T29 DI status
[14] T32 DI status
[15] T33 DI status
[16] T37 DI status
[21] Thermal
warning
[30] Brake fault
(IGBT)
[40] Out of ref
range
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic Rule 0
®
is a registered Danfoss trademark
Function:
The input will go high whenever T27 has
24 V and will go low whenever T27 has 0
V.
The input will go high whenever T29 has
24 V and will go low whenever T29 has 0
V.
The input will go high whenever T32 has
24 V and will go low whenever T32 has 0
V.
The input will go high whenever T33 has
24 V and will go low whenever T33 has 0
V.
The input will go high whenever T37 has
0 V and will go low whenever T37 has 24
V
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the Adjustable frequency drive, the
brake resistor, or the thermistor.
Will go high when the brake IGBT is short-
circuited.
If Comparator 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be
low.
If Comparator 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be
low.
If Comparator 1 is evaluated as TRUE, the
input will go high. Otherwise, it will be
low.
If Comparator 2 is evaluated as TRUE, the
input will go high. Otherwise, it will be
low.
If Comparator 3 is evaluated as TRUE, the
input will go high. Otherwise, it will be
low.
If Comparator 4 is evaluated as TRUE, the
input will go high. Otherwise, it will be
low.
If Comparator 5 is evaluated as TRUE, the
input will go high. Otherwise, it will be
low.
If Logic Rule 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be
low.