Start Up and Commissioning

4 Start Up and Commissioning

4.1 Pre-start

CAUTION
Before applying power to the unit, inspect the entire installation as detailed in Table 4.1. Check mark those items when
4
4
completed.
Inspect for
Auxiliary equipment
Cable routing
Control wiring
Cooling clearance
EMC considerations
Environmental consider-
ations
Fusing and circuit
breakers
Grounding
Input and output power
wiring
Panel interior
Switches
Vibration
Table 4.1 Start-up Checklist
36
Operating Instructions
Description
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers on the input
power side of the frequency converter or output side to the motor. Ensure that they are ready for
full speed operation.
Check function and installation of any sensors used for feedback to the frequency converter
Remove power factor correction caps on motors, if present
Use separate metallic conduits for each of the following:
input power
motor wiring
control wiring
Check for broken or damaged wires and loose connections
Check that control wiring is isolated from power and motor wiring for noise immunity
Check the voltage source of the signals, if necessary
The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated
correctly
Measure that top and bottom clearance is adequate to ensure proper air flow for cooling
Check for proper installation regarding electromagnetic compatibility
See equipment label for the maximum ambient operating temperature limits
Humidity levels must be 5–95% non-condensing
Check for proper fusing or circuit breakers
Check that all fuses are inserted firmly and in operational condition and that all circuit breakers are
in the open position
The unit requires a ground wire from its chassis to the building ground
Check for good ground connections that are tight and free of oxidation
Grounding to conduit or mounting the back panel to a metal surface is not a suitable ground
Check for loose connections
Check that motor and mains are in separate conduit or separated screened cables
Inspect that the unit interior is free of debris and corrosion
Ensure that all switch and disconnect settings are in the proper positions
Check that the unit is mounted solidly or that shock mounts are used, as necessary
Check for an unusual amount of vibration