Parameter Descriptions

3.8 Parameters: 6-** Analog In/Out

3.8.1 6-0* Analog I/O Mode

The analog inputs can freely be allocated to be either
voltage (FC 301: 0..10V, FC 302: 0..+/- 10V) or current (FC
301/FC 302: 0/4..20mA) input.
NOTE!
Thermistors may be connected to either an analog or a
digital input.
6-00 Live Zero Timeout Time
Range:
Function:
10 s
[1 -
Enter the Live Zero Timeout time period. Live Zero
*
99 s]
Timeout Time is active for analog inputs, i.e.,
terminal 53 or terminal 54, used as reference or
feedback sources. If the reference signal value
associated with the selected current input falls
below 50% of the value set in 6-10 Terminal 53
Low Voltage, 6-12 Terminal 53 Low Current,
6-20 Terminal 54 Low Voltage or 6-22 Terminal 54
Low Current for a time period longer than the time
set in 6-00 Live Zero Timeout Time, the function
selected in 6-01 Live Zero Timeout Function will be
activated.

6-01 Live Zero Timeout Function

Option:
Function:
Select the timeout function. The function set
in 6-01 Live Zero Timeout Function will be
activated if the input signal on terminal 53 or
54 is below 50% of the value in 6-10 Terminal
53 Low Voltage, 6-12 Terminal 53 Low Current,
6-20 Terminal 54 Low Voltage or 6-22 Terminal
54 Low Current for a time period defined in
6-00 Live Zero Timeout Time. If several
timeouts occur simultaneously, the Adjustable
frequency drive prioritizes the timeout
functions as follows:
1.
2.
[0]
Off
*
[1]
Freeze
Frozen at the present value
output
[2]
Stop
Overruled to stop
[3]
Jogging
Overruled to jog speed
[4]
Max. speed
Overruled to max. speed
[5]
Stop and
Overruled to stop with subsequent trip
trip
[20] Coast
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
6-01 Live Zero Timeout Function
8-04 Control Word Timeout Function
®
MG33MD22 - VLT
is a registered Danfoss trademark
6-01 Live Zero Timeout Function
Option:
Function:
[21] Coast and
trip

3.8.2 6-1* Analog Input 1

Parameters for configuring the scaling and limits for
analog input 1 (terminal 53).
Ref./Feedback
[RPM]
Par 6-xx
1500
'High Ref./
Feedb. Value'
1200
900
600
300
Par 6-xx
'Low Ref./
150
Feedb. Value'
Ex.
1 V
Par 6-xx
'Low Voltage'or
'Low Current'
6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V
[Application
Enter the low voltage value. This
*
dependant]
analog input scaling value should
correspond to the minimum reference
value, set in 6-14 Terminal 53 Low Ref./
Feedb. Value. See also the section
Reference Handling.
6-11 Terminal 53 High Voltage
Range:
Function:
10.00 V
[ par. 6-10 -
Enter the high voltage value. This
*
10.00 V]
analog input scaling value should
correspond to the high reference/
feedback value set in 6-15 Terminal 53
High Ref./Feedb. Value.
6-12 Terminal 53 Low Current
Range:
Function:
0.14
[Application
Enter the low current value. This
mA
dependant]
reference signal should correspond to
*
the minimum reference value, set in
3-02 Minimum Reference. The value
must be set at >2mA in order to
activate the Live Zero Timeout
Function in 6-01 Live Zero Timeout
Function.
5 V
10 V
Par 6-xx
Analog input
'High Voltage'or
'High Current'
3-69
3
3