Parameter Descriptions
10-12 Process Data Config Read
Select the process read data for I/O assembly instances 101/151.
Elements [2] and [3] of this array can be selected. Elements [0]
and [1] of the array are fixed.
Option:
[1684]
Comm. Option STW
[1690]
Alarm Word
[1691]
Alarm Word 2
[1692]
Warning Word
[1693]
Warning Word 2
[1694]
Ext. Status Word
[1860]
Digital Input 2
[3421]
PCD 1 Read from MCO
[3422]
PCD 2 Read from MCO
[3423]
PCD 3 Read from MCO
[3424]
PCD 4 Read from MCO
[3425]
PCD 5 Read from MCO
[3426]
PCD 6 Read from MCO
[3427]
PCD 7 Read from MCO
[3428]
PCD 8 Read from MCO
[3429]
PCD 9 Read from MCO
[3430]
PCD 10 Read from MCO
[3440]
Digital Inputs
[3441]
Digital Outputs
[3450]
Actual Position
[3451]
Commanded Position
[3452]
Actual Master Position
[3453]
Slave Index Position
[3454]
Master Index Position
[3455]
Curve Position
[3456]
Track Error
[3457]
Synchronizing Error
[3458]
Actual Velocity
[3459]
Actual Master Velocity
[3460]
Synchronizing Status
[3461]
Axis Status
[3462]
Program Status
[3464]
MCO 302 Status
[3465]
MCO 302 Control
[3470]
MCO Alarm Word 1
[3471]
MCO Alarm Word 2
[4280]
Safe Option Status
[4285]
Active Safe Func.
[4286]
Safe Option Info

10-13 Warning Parameter

Range:
Function:
0
[0 -
View a DeviceNet-specific warning word. One bit
*
65535 ]
is assigned to every warning. Please refer to the
DeviceNet Instruction Manual (MG.33.DX.YY) for
further information.
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
[0]
[1]
[0]
[1]

3.12.3 10-2* COS Filters

0
®
MG33MD22 - VLT
is a registered Danfoss trademark
10-13 Warning Parameter
Range:
Function:
Bit:
Meaning:
0
BusNetwork not active
1
Explicit connection timeout
2
I/O connection
3
Retry limit reached
4
Actual is not updated
5
CAN bus off
6
I/O send error
7
Initialization error
8
No bus supply
9
Bus off
10
Error passive
11
Error warning
12
Duplicate MAC ID Error
13
RX queue overrun
14
TX queue overrun
15
CAN overrun

10-14 Net Reference

Read only from LCP
Option:
Function:
Select the reference source in instance 21/71 and
20/70.
Off Enables reference via analog/digital inputs.
*
On Enables reference via the serial communication bus.

10-15 Net Control

Read only from LCP
Option:
Function:
Select the control source in Instance 21/71 and 20/70.
Off Enables control via analog/digital inputs.
*
On Enable control via the serial communication bus.
10-20 COS Filter 1
Range:
Function:
[0 - 65535 ] Enter the value for COS Filter 1 to set up the
*
filter mask for the status word. When operating
in COS (Change-Of-State), this function filters
out bits in the status word that should not be
sent if they change.
3
3
3-103