Parameter Descriptions
3-02 Minimum Reference
Range:
3-03 Maximum Reference
Range:
Application
[Application
dependent
dependant]
*
3-04 Reference Function
Option:
Function:
[0]
Sum
Sums both external and preset reference
*
sources.
[1]
External/Preset Use either the preset or the external
reference source.
Shift between external and preset via a
command on a digital input.

3.5.2 3-1* References

Select the preset reference(s). Select Preset ref. bit 0 / 1 / 2
[16], [17] or [18] for the corresponding digital inputs in
parameter group 5-1*.

3-10 Preset Reference

Array [8]
Range: 0-7
Range:
0.00 %
[-100.00 - 100.00 %]
*
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
Speed closed-loop [1], RPM;
for Torque [2], Nm.
The unit selected in
3-01 Reference/Feedback
Unit.
Function:
Enter the maximum reference. The
maximum reference is the highest
value obtainable by adding all
references together.
The Maximum Reference unit
matches:
The choice of configu-
ration in 1-00 Configuration
Mode: for Speed closed-loop
[1], RPM; for Torque [2],
Nm.
The unit selected in
3-00 Reference Range.
Function:
®
MG33MD22 - VLT
is a registered Danfoss trademark
Preset ref. bit
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
Preset ref. 4
Preset ref. 5
Preset ref. 6
Preset ref. 7
3-11 Jog Speed [Hz]
Range:
Application
[Application
dependent
dependant]
*
3-12 Catch up/slow Down Value
Range:
0.00 %
[0.00 - 100.00 %]
*

3-13 Reference Site

Option:
Function:
Select which reference site to activate.
[0]
Linked to
Use local reference when in hand mode; or
*
Hand / Auto
remote reference when in auto mode.
[1]
Remote
Use remote reference in both hand mode
and auto mode.
[2]
Local
Use local reference in both hand mode and
auto mode.
NOTE!
When set to Local [2], the Adjustable
frequency drive will start with this
setting again following a 'power-down'.
2
1
0
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1
Function:
The jog speed is a fixed
output speed at which the
Adjustable frequency drive is
running when the jog
function is activated.
See also 3-80 Jog Ramp Time.