Parameter Descriptions

3.5 Parameters: 3-** Reference / Ramps

Parameters for reference handling, definition of limitations,
and configuration of the reaction of the Adjustable
3
3
frequency drive to changes.

3.5.1 3-0* Reference Limits

3-00 Reference Range

Option:
[0]
Min -
Max
[1]
-Max -
*
+Max

3-01 Reference/Feedback Unit

Option:
[0]
None
*
[1]
%
[2]
RPM
[3]
Hz
[4]
Nm
[5]
PPM
[10]
1/min
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
3-34
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
Select the range of the reference signal and the
feedback signal. Signal values can be positive
only, or positive and negative. The minimum
limit may have a negative value, unless Speed
closed-loop [1] control or Process [3] is selected in
1-00 Configuration Mode.
Select the range of the reference signal and the
feedback signal. Signal values can be positive
only, or positive and negative. The minimum
limit may have a negative value, unless Speed
closed-loop [1] control or Process [3] is selected in
1-00 Configuration Mode.
For both positive and negative values (both
directions, relative to 4-10 Motor Speed Direction).
Function:
Select the unit to be used in process PID control
references and feedback. 1-00 Configuration Mode
must be either [3] Process or [8] Extended PID
Control.
MG33MD22 - VLT
3-01 Reference/Feedback Unit
Option:
Function:
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[150] lb ft
[160] °F
[170] psi
[171] lb/in²
[172] in WG
[173] ft WG
[180] HP

3-02 Minimum Reference

Range:
Application
dependent
[Application
*
dependant]
®
is a registered Danfoss trademark
Function:
Enter the Minimum Reference. The
Minimum Reference is the lowest
value obtainable by summing all
references.
Minimum Reference is active only
when 3-00 Reference Range is set to
Min.- Max. [0].
The minimum reference unit
matches:
The choice of configuration
in 1-00 Configuration Mode
Configuration Mode: for