Parameter Descriptions
moment of inertia of the rotor and the iron loss resistance
(1-36 Iron Loss Resistance (Rfe)).
Parameter groups 1-3* and 1-4* cannot be adjusted while
the motor is running.
P 1-33
P 1-30
I
X
1
R
s
U
1
P 1-36
R
Fe
Figure 3.1 Motor equivalent diagram for an asynchronous
motor
NOTE!
A simple check of the X1 + Xh sum value is to divide the
line to line motor voltage by the sqrt(3) and divide this
value by the motor no load current. [VL-L/sqrt(3)]/I
+ Xh. These values are important to properly magnetize
the motor. For high pole motors it is highly recommended
to perform this check.
1-30 Stator Resistance (Rs)
Range:
Application dependent
*

1-31 Rotor Resistance (Rr)

Range:
Application
[Application
dependent
dependant]
*
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
P 1-34
X'
P 1-35
P 1-31
X
R'
h
r
= X1
NL
Function:
[Application dependant]
Function:
Fine-tuning R
will improve shaft
r
performance. Set the rotor
resistance value using one of these
methods:
1.
Run an AMA on a cold
motor. The Adjustable
frequency drive will
measure the value from
the motor. All compen-
sations are reset to 100%.
2.
Enter the R
value
r
manually. Obtain the value
from the motor supplier.
3.
Use the R
default setting.
r
The Adjustable frequency
drive establishes the
setting on the basis of the
motor nameplate data.
®
MG33MD22 - VLT
is a registered Danfoss trademark

1-33 Stator Leakage Reactance (X1)

Range:
Function:
Application
[Application
Set the stator leakage reactance of
dependent
dependant]
the motor using one of these
*
methods:
1-34 Rotor Leakage Reactance (X2)
Range:
Application dependent
[Application dependant]
*

1-35 Main Reactance (Xh)

Range:
Function:
Application
[Application
Set the main reactance of the
dependent
dependant]
motor using one of these methods:
*
1-36 Iron Loss Resistance (Rfe)
Range:
Application dependent
[Application dependant]
*
1-37 d-axis Inductance (Ld)
Range:
Application dependent
[Application dependant]
*
1.
Run an AMA on a cold
motor. The Adjustable
frequency drive will
measure the value from
the motor.
2.
Enter the X
value
1
manually. Obtain the
value from the motor
supplier.
3.
Use the X
default setting.
1
The Adjustable frequency
drive establishes the
setting on the basis of the
motor nameplate data.
Function:
1.
Run an AMA on a cold
motor. The Adjustable
frequency drive will
measure the value from
the motor.
2.
Enter the X
value
h
manually. Obtain the value
from the motor supplier.
3.
Use the X
default setting.
h
The Adjustable frequency
drive establishes the
setting on the basis of the
motor nameplate data.
Function:
Function:
3-17
3
3