35-25 Term. X48/7 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/7. The temperature limits
can be set in 35-26 Term. X48/7 Low Temp. Limit and 35-27 Term.
X48/7 High Temp. Limit.
Option:
[0]
Disabled
*
[1]
Enabled
35-26 Term. X48/7 Low Temp. Limit
Range:
Application dependent
*
35-27 Term. X48/7 High Temp. Limit
Range:
Application dependent
*

3.21.4 35-3* Temp. Input X48/10 (MCB 114)

35-34 Term. X48/10 Filter Time Constant
Range:
Function:
0.001 s
[0.001 -
Enter the filter time constant. This is a
*
10.000 s]
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/10. A high time constant
value improves dampening but also
increases the time delay through the
filter.

35-35 Term. X48/10 Temp. Monitor

This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/10. The temperature limits
can be set in 35-36 Term. X48/10 Low Temp. Limit/35-37 Term.
X48/10 High Temp. Limit.
Option:
[0]
Disabled
*
[1]
Enabled
35-36 Term. X48/10 Low Temp. Limit
Range:
Application dependent
*
35-37 Term. X48/10 High Temp. Limit
Range:
Application dependent
*
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
Function:
[Application dependant]
Function:
[Application dependant]
Function:
Function:
[Application dependant]
Function:
[Application dependant]
®
MG33MD22 - VLT
is a registered Danfoss trademark

3.21.5 35-4* Analog Input X48/2 (MCB 114)

35-42 Term. X48/2 Low Current

Range:
Function:
4.00
[Application
Enter the current (mA) that
mA
dependant]
corresponds to the low reference
*
value, set in 35-44 Term. X48/2 Low
Ref./Feedb. Value. The value must be
set at > 2mA in order to activate the
Live Zero Timeout Function in
6-01 Live Zero Timeout Function.
35-43 Term. X48/2 High Current
Range:
20.00 mA
[Application
*
dependant]
35-44 Term. X48/2 Low Ref./Feedb. Value
Range:
Function:
0.000
[-999999.999 -
Enter the reference or feedback
*
999999.999 ]
value (in RPM, Hz, bar, etc.) that
corresponds to the voltage or
current set in 35-42 Term. X48/2
Low Current.
35-45 Term. X48/2 High Ref./Feedb. Value
Range:
100.000
[-999999.999 -
*
999999.999 ]
35-46 Term. X48/2 Filter Time Constant
Range:
Function:
0.001 s
[0.001 -
Enter the filter time constant. This is a
*
10.000 s]
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/2. A high time constant
value improves dampening but also
increases the time delay through the
filter.
Function:
Enter the current (mA) that
corresponds to the high
reference value (set in
35-45 Term. X48/2 High Ref./Feedb.
Value).
Function:
Enter the reference or feedback
value (in RPM, Hz, bar, etc.) that
corresponds to the voltage or
current set in 35-43 Term. X48/2
High Current.
3-155