Parameter Descriptions
[4]
Enable / no
Ready for operation. No start or stop
warning
command is been given (start/disable).
No warnings are active.
[5]
VLT running
Motor is running and shaft torque is
present.
[6]
Running / no
Output speed is higher than the speed
set in 1-81 Min Speed for Function at Stop
warning
[RPM]. The motor is running and there are
no warnings.
[7]
Run in
Motor is running within the programmed
range/no
current and speed ranges set in
warning
4-50 Warning Current Low to 4-53 Warning
Speed High. There are no warnings.
[8]
Run on
Motor runs at reference speed. No
reference / no
warnings.
warning
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
An alarm or a warning activates the
warning
output.
[11]
At torque limit
The torque limit set in 4-16 Torque Limit
Motor Mode or 4-17 Torque Limit Generator
Mode has been exceeded.
[12]
Out of current
The motor current is outside the range
range
set in 4-18 Current Limit.
[13]
Below current,
Motor current is lower than set in
low
4-50 Warning Current Low.
[14]
Above current,
Motor current is higher than set in
high
4-51 Warning Current High.
[15]
Out of speed
Output frequency is outside the
range
frequency ranges set in 4-52 Warning
Speed Low and 4-53 Warning Speed High.
[16]
Below speed,
Output speed is lower than the setting in
low
4-52 Warning Speed Low.
[17]
Above speed,
Output speed is higher than the setting
high
in 4-53 Warning Speed High.
[18]
Out of
Feedback is outside the range set in
feedback range
4-56 Warning Feedback Low and
4-57 Warning Feedback High.
[19]
Below
Feedback is below the limit set in
feedback low
4-56 Warning Feedback Low.
[20]
Above
Feedback is above the limit set in
feedback high
4-57 Warning Feedback High.
[21]
Thermal
The thermal warning turns on when the
warning
temperature exceeds the limit in the
motor, the Adjustable frequency drive,
the brake resistor, or the thermistor.
[22]
Ready, no
Adjustable frequency drive is ready for
thermal
operation and there is no over-
warning
temperature warning.
[23]
Remote, ready,
Adjustable frequency drive is ready for
no thermal
operation and is in [Auto on] mode.
warning
There is no over-temperature warning.
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[40]
[41]
[42]
[43]
[45]
[46]
®
MG33MD22 - VLT
is a registered Danfoss trademark
Ready, voltage
Adjustable frequency drive is ready for
OK
operation and the AC line voltage is
within the specified voltage range (see
General Specifications section in the
Design Guide).
Reverse
Reversing. Logic '1' when CW rotation of
the motor. Logic '0' when CCW rotation
of the motor. If the motor is not rotating,
the output will follow the reference.
Bus OK
Active communication (no timeout) via
the serial communication port.
Torque limit
Use in performing a coasting stop and in
and stop
torque limit condition. If the Adjustable
frequency drive has received a stop signal
and is at the torque limit, the signal is
Logic '0'.
Brake, no brake
Brake is active and there are no warnings.
warning
Brake ready, no
Brake is ready for operation and there are
fault
no faults.
Brake fault
Output is Logic '1' when the brake IGBT is
(IGBT)
short-circuited. Use this function to
protect the Adjustable frequency drive if
there is a fault on the brake modules. Use
the output/relay to cut out the AC line
voltage from the Adjustable frequency
drive.
Relay 123
The relay is activated when Control Word
[0] is selected in parameter group 8-**.
Mechanical
Enables control of an external mechanical
brake control
brake, see description in the section
Control of Mechanical Brake, and
parameter group 2-2*
Safe stop
Indicates that the safe stop on terminal
activated (FC
37 has been activated.
302 only)
Out of ref
Active when the actual speed is outside
range
settings in 4-52 Warning Speed Low to
4-55 Warning Reference High.
Below
Active when actual speed is below speed
reference low
reference setting.
Above
Active when actual speed is above speed
reference high
reference setting
Extended PID
Limit
Bus Ctrl
Controls output via bus. The state of the
output is set in 5-90 Digital & Relay Bus
Control. The output state is retained in
the event of bus timeout.
Bus Ctrl On at
Controls output via bus. The state of the
timeout
output is set in 5-90 Digital & Relay Bus
Control. In the event of a bus timeout,
the output state is set high (On).
3
3
3-55