Parameter Descriptions

1-84 Precise Stop Counter Value

Range:
100000
[0 - 999999999 ] Enter the counter value to be used
*
3
3

1-85 Precise Stop Speed Compensation Delay

Range:
10 ms
[0 - 100
*
ms]

3.3.9 1-9* Motor Temperature

1-90 Motor Thermal Protection

Option:
3-24
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
in the integrated precise stop
function, 1-83 Precise Stop Function.
The maximum permissible frequency
at terminal 29 or 33 is 110kHz.
Not used for selection [0] and [3] in
1-83 Precise Stop Function
Function:
Enter the delay time for sensors, PLCs, etc.
for use in 1-83 Precise Stop Function. In
speed compensated stop mode, the delay
time at different frequencies has a major
influence on the stop function.
Not used for selection [0], [1] and [2] in
1-83 Precise Stop Function
Function:
Thermal motor protection can be
implemented using a range of techniques:
Via a PTC sensor in the motor
windings connected to one of the
analog or digital inputs
(1-93 Thermistor Source). See
3.3.10.1 PTC Thermistor Connection.
Via a KTY sensor in the motor
winding connected to an analog
input (1-96 KTY Thermistor Resource).
See 3.3.10.2 KTY Sensor Connection.
Via calculation (ETR = Electronic
Thermal Relay) of the thermal load,
based on the actual load and time.
The calculated thermal load is
compared with the rated motor
current I
and the rated motor
M,N
frequency f
. See 3.3.10.3 ETR and
M,N
3.3.10.4 ATEX ETR.
Via a mechanical thermal switch
(Klixon type). See 3.3.10.5 Klixon.
For the North American market: The ETR
functions provide class 20 motor overload
protection in accordance with NEC.
MG33MD22 - VLT
1-90 Motor Thermal Protection
Option:
Function:
[0]
No
Continuously overloaded motor, when no
*
protection
warning or trip of the Adjustable frequency
drive is required.
[1]
Thermistor
Activates a warning when the connected
warning
thermistor or KTY sensor in the motor reacts
in the event of motor overtemperature.
[2]
Thermistor
Stops (trips) Adjustable frequency drive when
trip
connected thermistor or KTY sensor in the
motor reacts in the event of motor overtem-
perature.
The thermistor cut-out value must be > 3
kΩ.
Integrate a thermistor (PTC sensor) in the
motor for winding protection.
[3]
ETR warning
Calculates the load when set-up 1 is active
1
and activates a warning on the display when
the motor is overloaded. Program a warning
signal via one of the digital outputs.
[4]
ETR trip 1
Calculates the load when set-up 1 is active
and stops (trips) Adjustable frequency drive
when the motor is overloaded. Program a
warning signal via one of the digital outputs.
The signal appears in the event of a warning
and if the Adjustable frequency drive trips
(thermal warning).
[5]
ETR warning
2
[6]
ETR trip 2
[7]
ETR warning
3
[8]
ETR trip 3
[9]
ETR warning
4
[10] ETR trip 4
[20] ATEX ETR
Activates the thermal monitoring function for
Ex-e motors for ATEX. Enables 1-94 ATEX ETR
cur.lim. speed reduction, 1-98 ATEX ETR
interpol. points freq. and 1-99 ATEX ETR
interpol points current.
[21] Advanced
ETR
NOTE!
If [20] is selected, follow the instructions exactly as
described in the dedicated chapter in the VLT
AutomationDrive design guide and the instructions given
by the motor manufacturer.
®