Parameter Descriptions
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Application
[-999999.999 -
dependent
999999.999
*
ReferenceFeed-
backUnit]
Application
[-999999.999 -
dependent
999999.999
*
ReferenceFeed-
backUnit]
6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.001 s
[0.001 -
Enter the time constant. This is a first-
*
10.000 s]
order digital low pass filter time
constant for suppressing electrical noise
in terminal 54. A high time constant
value improves dampening but also
increases the time delay through the
filter.
NOTE!
This parameter cannot be adjusted while the motor is
running.
3.8.4 6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for
analog input 3 (X30/11) placed on option module MCB
101.
6-30 Terminal X30/11 Low Voltage
Range:
Function:
0.07 V
[
0.00 - par.
Sets the analog input scaling value to
*
6-31 V]
correspond to the low reference/
feedback value (set in 6-34 Term.
X30/11 Low Ref./Feedb. Value).
6-31 Terminal X30/11 High Voltage
Range:
10.00 V
[
par. 6-30 -
Sets the analog input scaling value to
*
10.00 V]
correspond to the high reference/
feedback value (set in 6-35 Term.
X30/11 High Ref./Feedb. Value).
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
Enter the analog input
scaling value that
corresponds to the
maximum reference
feedback value set in
3-03 Maximum Reference.
Enter the analog input
scaling value that
corresponds to the
maximum reference
feedback value set in
3-03 Maximum Reference.
Function:
®
MG33MD22 - VLT
is a registered Danfoss trademark
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
0.000
[-999999.999 -
*
999999.999 ]
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
100.000
[-999999.999 -
*
999999.999 ]
6-36 Term. X30/11 Filter Time Constant
Range:
Function:
0.001 s
[0.001 - 10.000 s] A 1
*
time constant for suppressing
electrical noise on terminal X30/11.
NOTE!
This parameter cannot be changed while the motor is
running.
3.8.5 6-4* Analog Input 4 MCB 101
Parameter group for configuring the scale and limits for
analog input 4 (X30/12) placed on option module MCB
101.
6-40 Terminal X30/12 Low Voltage
Range:
Function:
0.07 V
[
0.00 - par.
Sets the analog input scaling value to
*
6-41 V]
correspond to the low reference/
feedback value set in 6-44 Term.
X30/12 Low Ref./Feedb. Value.
6-41 Terminal X30/12 High Voltage
Range:
Function:
10.00 V
[
par. 6-40 -
Sets the analog input scaling value to
*
10.00 V]
correspond to the high reference/
feedback value set in 6-45 Term.
X30/12 High Ref./Feedb. Value.
6-44 Term. X30/12 Low Ref./Feedb. Value
Range:
0.000
[-999999.999 -
*
999999.999 ]
Function:
Sets the analog input scaling
value to correspond to the low
voltage value (set in 6-30 Terminal
X30/11 Low Voltage).
Function:
Sets the analog input scaling
value to correspond to the high
voltage value (set in
6-31 Terminal X30/11 High
Voltage).
st
order digital low pass filter
Function:
Sets the analog output scaling
value to correspond to the low
voltage value set in 6-40 Terminal
X30/12 Low Voltage.
3-71
3
3