Parameter Descriptions
Decrease or Clear. To activate the function, at least one
digital input must be set up to Increase or Decrease.
3-90 Step Size
Range:
0.10 %
[0.01 - 200.00 %]
*

3-91 Ramp Time

Range:
Function:
1.00
[0.00 -
Enter the ramp time, i.e., the time for
s
3600.00 s]
adjustment of the reference from 0% to
*
100% of the specified digital potentiometer
function (Increase, Decrease or Clear).
If Increase/Decrease is activated for longer
than the ramp delay period specified in
3-95 Ramp Delay, the actual reference will be
ramped up/down according to this ramp
time. The ramp time is defined as the time
used to adjust the reference by the step size
specified in 3-90 Step Size.

3-92 Power Restore

Option:
Function:
[0]
Off Resets the Digital Potentiometer reference to 0% after
*
power-up.
[1]
On Restores the most recent Digital Potentiometer
reference at power-up.

3-93 Maximum Limit

Range:
Function:
100 %
[-200 - 200
Set the maximum permissible value for
*
%]
the resultant reference. This is advisable if
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
3-93 Maximum Limit
Range:
3-94 Minimum Limit
Range:
-100 %

3-95 Ramp Delay

Range:
Application
dependent
Function:
®
MG33MD22 - VLT
is a registered Danfoss trademark
Function:
the Digital Potentiometer is used for fine
tuning of the resulting reference.
Function:
[-200 - 200
Set the minimum permissible value for
*
%]
the resultant reference. This is advisable
if the Digital Potentiometer is used for
fine tuning of the resulting reference.
Function:
[Application
Enter the delay required from
dependant]
activation of the digital potenti-
*
ometer function until the
Adjustable frequency drive starts
to ramp the reference. With a
delay of 0 ms, the reference
starts to ramp as soon as
INCREASE/DECREASE is activated.
See also 3-91 Ramp Time.
3
3
3-43