Parameter Descriptions
3.17.4 16-6* Inputs & Outputs

16-60 Digital Input

3
3
Range:
Function:
0
[0 -
View the signal states from the active digital inputs.
1023 ]
Example: Input 18 corresponds to bit no. 5, '0' = no
*
signal, '1' = connected signal. Bit 6 works in the
opposite way, on = '0', off = '1' (safe stop input).
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10-63
0 0
16-61 Terminal 53 Switch Setting
Option:
[0]
Current
*
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]

16-62 Analog Input 53

Range:
0.000
[-20.000 - 20.000 ]
*
3-144
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Digital input term. 33
Digital input term. 32
Digital input term. 29
Digital input term. 27
Digital input term. 19
Digital input term. 18
Digital input term. 37
Digital input GP I/O term. X30/4
Digital input GP I/O term. X30/3
Digital input GP I/O term. X30/2
Reserved for future terminals
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0
D I T - 3 3
D I T - 3 2
D I T - 2 9
D I T - 2 7
D I T - 1 9
D I T - 1 8
D I T - 3 7
D I X 3 0/4
D I X 3 0/3
D I X 3 0/2
D I X 4 6/ 1 3
D I X 4 6/ 1 1
D I X 4 6/9
D I X 4 6/ 7
D I X 4 6/ 5
D I X 4 6/3
D I X 4 6/ 1
Function:
View the setting of input terminal 53. Current
= 0; Voltage = 1.
Function:
View the actual value at input 53.
MG33MD22 - VLT
16-63 Terminal 54 Switch Setting
Option:
Function:
View the setting of input terminal 54. Current
= 0; Voltage = 1.
[0]
Current
*
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
16-64 Analog Input 54
Range:
0.000
[-20.000 - 20.000 ]
*
16-65 Analog Output 42 [mA]
Range:
0.000
[0.000 - 30.000 ] View the actual value at output 42 in
*
16-66 Digital Output [bin]
Range:
Function:
0
[0 - 15 ]
View the binary value of all digital outputs.
*
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
[0 - 130000 ] View the actual frequency rate on terminal
*
29.
16-68 Freq. Input #33 [Hz]
Range:
Function:
0
[0 - 130000 ] View the actual value of the frequency
*
applied at terminal 33 as an impulse input.
16-69 Pulse Output #27 [Hz]
Range:
Function:
0
[0 - 40000 ] View the actual value of pulses applied to
*
terminal 27 in digital output mode.
16-70 Pulse Output #29 [Hz]
Range:
Function:
0
[0 - 40000 ] View the actual value of pulses at terminal 29
*
in digital output mode.
This parameter is available for FC 302 only.
®
is a registered Danfoss trademark
Function:
View the actual value at input 54.
Function:
mA. The value shown reflects the
selection in 6-50 Terminal 42 Output.