Parameter Descriptions

9-28 Process Control

Option:
3
3
[0]
Disable
[1]
Enable
*
cyclic
master
9-44 Fault Message Counter
Range:
0
[0 - 65535 ] This parameter displays the number of error
*
9-45 Fault Code
Range:
0
[0 - 0 ] This buffer contains the alarm word for all alarms
*
and warnings that have occurred since the last
reset or power-up. The maximum buffer capacity is
eight error events.
9-47 Fault Number
Range:
0
[0 - 0 ] This buffer contains the alarm number (e.g., 2 for
*
live zero error, 4 for line phase loss) for all alarms
and warnings that have occurred since last reset or
power-up. The maximum buffer capacity is eight
error events.
9-52 Fault Situation Counter
Range:
0
[0 - 1000 ] This parameter displays the number of error
*
3-98
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
Function:
Process control (setting of the control word,
speed reference, and process data) is possible
via either Profibus or standard serial communi-
cation bus but not both simultaneously. Local
control is always possible via the LCP. Control
via process control is possible via either
terminals or serial communication bus
depending on the settings in 8-50 Coasting
Select to 8-56 Preset Reference Select.
Disables process control via Profibus, and
enables process control via standard serial
communication bus or Profibus Master class 2.
Enables process control via Profibus Master Class
1, and disables process control via standard
serial communication bus or Profibus Master
class 2.
Function:
events stored in 9-45 Fault Code and 9-47 Fault
Number. The maximum buffer capacity is eight
error events. The buffer and counter are set to
0 upon reset or power-up.
Function:
Function:
Function:
events which have occurred since the last reset
of power-up.
MG33MD22 - VLT
FC 300 Programming Guide

9-53 Profibus Warning Word

Range:
0
[0 - 65535 ] This parameter displays Profibus communi-
*
Read only
Bit:
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

9-63 Actual Baud Rate

Option:
[0]
[1]
[2]
[3]
[4]
[6]
[7]
[8]
[9]
[10]
[11]
[255]
*

9-64 Device Identification

Range:
0
[0 - 0 ] This parameter displays the device identification.
*
®
is a registered Danfoss trademark
Function:
cation warnings. Please refer to the Profibus
Instruction Manual for further information.
Meaning:
Connection with DP master is not ok
Not used
FDLNDL (Serial Communication Bus Data link Layer) is
not ok
Clear data command received
Actual value is not updated
Baudrate search
PROFIBUS ASIC is not transmitting
Initialization of PROFIBUS is not ok
Adjustable frequency drive is tripped
Internal CAN error
Wrong configuration data from PLC
Wrong ID sent by PLC
Internal error occured
Not configured
Timeout active
Warning 34 active
Function:
This parameter displays the actual
Profibus baud rate. The Profibus
Master automatically sets the baud
rate.
9,6 kbit/s
19,2 kbit/s
93,75 kbit/s
187,5 kbit/s
500 kbit/s
1500 kbit/s
3000 kbit/s
6000 kbit/s
12000 kbit/s
31,25 kbit/s
45,45 kbit/s
No baudrate found
Function:
Please refer to the Instruction Manual for Profibus,
MG.33.CX.YY for further explanation.