Parameter Descriptions
3.12 Parameters: 10-** DeviceNet CAN
Fieldbus

3.12.1 10-0* Common Settings

10-00 CAN Protocol
Option:
Function:
[0]
CANopen
[1]
DeviceNet
View the active CAN protocol.
*
NOTE!
The options depend on installed option.
10-01 Baud Rate Select
Select the serial communication bus transmission speed. The
selection must correspond to the transmission speed of the
master and the other serial communication bus nodes.
Option:
[16]
10 Kbps
[17]
20 Kbps
[18]
50 Kbps
[19]
100 Kbps
[20]
125 Kbps
*
[21]
250 Kbps
[22]
500 Kbps
10-02 MAC ID
Range:
Application
[Application
dependent
dependant]
*
10-05 Readout Transmit Error Counter
Range:
Function:
0
[0 - 255 ] View the number of CAN control transmission
*
errors since the last power-up.
10-06 Readout Receive Error Counter
Range:
Function:
0
[0 - 255 ] View the number of CAN control receipt errors
*
since the last power-up.
10-07 Readout Bus Off Counter
Range:
Function:
0
[0 - 255 ] View the number of Bus Off events since the last
*
power-up.
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
Function:
Selection of station address.
Every station connected to
the same network must have
an unambiguous address.
®
MG33MD22 - VLT
is a registered Danfoss trademark
3.12.2 10-1* DeviceNet

10-10 Process Data Type Selection

Option:
Function:
Select the Instance (message) for data
transmission. The instances available are
dependent upon the setting of 8-10 Control
Profile.
When 8-10 Control Profile is set to [0] FC
profile, 10-10 Process Data Type Selection
options [0] and [1] are available.
When 8-10 Control Profile is set to [5] ODVA,
10-10 Process Data Type Selection options [2]
and [3] are available.
Instances 100/150 and 101/151 are Danfoss-
specific. Instances 20/70 and 21/71 are
ODVA-specific AC Drive profiles.
For guidelines in message selection, please
refer to the DeviceNet Instruction Manual.
Note that a change to this parameter will
be executed immediately.
[0]
INSTANCE
*
100/150
[1]
INSTANCE
101/151
[2]
INSTANCE
20/70
[3]
INSTANCE
21/71
10-11 Process Data Config Write
Select the process write data for I/O assembly instances 101/151.
Elements [2] and [3] of this array can be selected. Elements [0]
and [1] of the array are fixed.
Option:
[0]
None
*
[302]
Minimum Reference
[303]
Maximum Reference
[312]
Catch up/slow Down Value
[341]
Ramp 1 Ramp up Time
[342]
Ramp 1 Ramp Down Time
[351]
Ramp 2 Ramp up Time
[352]
Ramp 2 Ramp down Time
[380]
Jog Ramp Time
[381]
Quick Stop Ramp Time
[411]
Motor Speed Low Limit [RPM]
[412]
Motor Speed Low Limit [Hz]
[413]
Motor Speed High Limit [RPM]
[414]
Motor Speed High Limit [Hz]
[416]
Torque Limit Motor Mode
[417]
Torque Limit Generator Mode
[590]
Digital & Relay Bus Control
3
3
Function: