Word N+1 Bit 11: Transmission Control Bit (All Tasks) - Omron C200H-MC221 Operation Manual

Motion control unit
Hide thumbs Also See for C200H-MC221:
Table of Contents

Advertisement

Interface Bit Specifics
Example Operation

6-5-11 Word n+1 Bit 11: Transmission Control Bit (All Tasks)

Signal
Timing Chart
144
In this example, the X-axis is moved to X100, so the X target position (the com-
mand's current position) is 100. Actually, a servo is used and a varying deviation
from 100 develops. The actual current position from the encoder reflects this
deviation.
Position
This bit is used to write data to the MC Unit.
The completion of data writing to the MC Unit can be confirmed with the Trans-
mission Completed Flag.
This bit must be on hold until the Transmission Completed Flag is turned ON.
This bit is available when the expansion data area is valid.
Data cannot be written to the MC Unit, read from the MC Unit, and written to the
flash memory at the same time. If they are instructed together, the instructions
are executed in the following order.
Priority: Data written to the MC Unit, data read from the MC Unit, and data written
to the flash memory.
The data transmission settings have the following functions.
Signal
Writes Data
Data is prepared in the
PC's data memory.
Required
information
No. of transfer words (I)
is set in the
expansion
data area.
Source word (I+1)
Destination address (I+2)
Transmission Control Bit
(n+1 bit 11)
Transmission Completed
Flag (n+8 bit 06)
Note Refer to Section 4 MC Unit Data.
Target position (the command's current position)
Current position (feedback value)
Function
Set
Set
Set
Set
40 ms min.
(Depends on the volume of data.)
Section 6-5
Time
Free
Free
Free
Free