Commissioning the DP master

3.2.1

Commissioning and communications for the master

How is a
The procedure on how to establish communications between the
communications
master and slave is shown using an example with the following
established
prerequisites:
between the
Assumptions and prerequisites:
master and the
S
slave?
S
S
S
How communications are established:
1. Open the existing SIMATIC project.
2. In the hardware Catalog under PROFIBUS–DP, add the station
3. Set the PROFIBUS address under properties.
4. Set the I/O address
5. Close the project and transfer to the master.
6. Power–up the drive and check the LED.
Note
The DP master can now communicate with the SIMODRIVE
POSMO A DP slave which has been powered–up.
E Siemens AG 2013 All Rights Reserved
SIMODRIVE POSMO A User Manual (POS1) – 08/2013 Edition
The master is a SIMATIC S7–315–2 DP.
The prerequisites for commissioning are fulfilled
(refer to Chapter 3.1).
The "DP slave POSMO A" should be integrated into an existing
SIMATIC S7 project.
The GSD file for the "DP slave POSMO A" is available and installed
(refer to Chapter 4.4.2).
"SIMODRIVE POSMO A".
The same address must be set at the positioning motor (DP slave)
using switch S1 (refer to Chapter 2.3.1).
Part
I address
O address
PKW
256–263
256–263 (each 8 bytes, addresses are only
an example)
PZD
264–267
264–267 (each 4 bytes, addresses are only
an example)
Does the LED have a steady green light?
yes
––> Normal operation, communications is error–free
no
––> Evaluate the status of the LED (refer to Chapter 6.1)
The drive itself identifies the selected baud rate.
3 Commissioning
3.2 Commissioning the DP master
3
3-75