02.99
Table 4-5
Description of the individual signals in the control word (STW) for the pos mode
Bit
Signal name
2
Operating condition/OFF 3
Enable operation/
Enable operation/
3
inhibit operation
Operating condition for pro-
Operating condition for pro-
4
gram/stop
Operating condition for pro-
5
gram/intermediate stop
Activate traversing task
Activate traversing task
6
6
(edge)
7
7
Reset the fault memory
Reset the fault memory
8
Jogging 1 ON/jogging 1 OFF
E Siemens AG 2013 All Rights Reserved
SIMODRIVE POSMO A User Manual (POS1) – 08/2013 Edition
4 Communications via PROFIBUS–DP
Signal status, signal description
1
Operating Condition
Ready
0
OFF 3
Deceleration along the current limit, power disconnected
from the motor, tracking operation, power–on inhibit
1
Enable operation
Ready
0
Inhibit operation
Power disconnected from the motor, motor coasts down,
"operation inhibited" status
1
Operating condition for program
The signal must be continuously present in order to execute
a traversing task.
0
Stop
Deceleration along the current limit.
The motor remains stationary with the holding torque.
The actual traversing task is rejected.
1
Operating condition for program
The signal must be continuously present in order to execute
a traversing task.
0
Intermediate stop
The drive brakes from an active traversing task along the
ramp to n = 0 and then remains stationary with the holding
torque.
The traversing task is not rejected.
For a change to bit 5 = 1, the traversing task is continued.
1/0
Each edge enables a traversing task or a new setpoint
(toggle bit).
An edge change may only be realized if bit 12 of the status
An edge change may only be realized if bit 12 of the status
word is used to acknowledge that the previous traversing
word is used to acknowledge that the previous traversing
0/1
task was accepted.
A program start is valid as a traversing task.
1
Acknowledge faults (0/1 edge)
Refer to Chapter 6.2
0
1
Jogging 1 ON
If operation is enabled and positioning is not active ––> the
drive traverses closed–loop speed controlled with jogging
setpoint 1.
––> Refer to Chapter 5.4.1
0
Jogging 1 OFF
4.2 Process data (PZD area)
4-105
4