Jogging: Jogging not possible
Cause
Drive not enabled.
Jogging already selected.
Traversing block being processed.
Note:
Additional information? ––> evaluate P954
Remedy
Acknowledgement
not required
Stop response
None
806 / P953.6
Referencing: Position not accepted
Cause
When referencing, the position was not accepted.
Motor moving (ZSW.13 = 1).
Drive not enabled.
Traversing block being processed.
After power-on: The motor has still not moved.
Note:
Additional information? ––> evaluate P954
Remedy
The motor must be stationary and closed-loop controlled.
Acknowledgement
not required
Stop response
None
807 / P953.7
Speed controller at stop
Cause
The speed controller is at its limit for more than 200 ms.
The required speed is not reached.
The load or friction is too high or the drive is too small.
The current limit (P28, P16) is set too low.
The drive is defective.
For the "traverse to fixed endstop" function, this warning is output when
the fixed endstop is reached.
Note:
The warning is only signaled if the appropriate fault is suppressed.
Remedy
Reduce load.
Increase current limit.
Replace the positioning motor.
Acknowledgement
not required
Stop response
None
808 / P953.8
Start absolute block not possible
Cause
A block with absolute position data can only be started for a referenced
drive.
Remedy
Reference drive.
Acknowledgement
not required
Stop response
None