05.03
02.99
Selection
The master selects the traversing block to be started by entering the
block number
required block number into this control byte.
(AnwSatz)
The selection becomes effective, if:
S
S
S
Start byte
The start byte is compared with a bit mask "SMStart" (P86:x) pro-
(STB)
grammed in a traversing block.
This means that the program sequence can be influenced via the start
byte.
S
S
Control word
The master issues its commands to the slave using control word STW.
(STW)
(n–set mode)
Table 4-6
Structure of the control word (STW) for the n–set mode
Open holding brake/close holding brake (from SW 1.4)
Bit
15
14
13
12
Ramp–function generator start/ramp–function generator stop
Note:
1 signal/0 signal
Note:
S
The signals designated in this way must have at least a "1" signal in order to be able to
operate a motor.
E Siemens AG 2013 All Rights Reserved
SIMODRIVE POSMO A User Manual (POS1) – 08/2013 Edition
If neither a traversing block nor program is active.
The program or the traversing block has been completely executed.
The program or the traversing block was canceled by an external
signal or a fault.
P86:x (high byte) = 0:
The block is not influenced by the start byte.
P86:x (high byte) > 0:
The block can only be started if the bits, set in P86:x (high byte), are
also set in the start byte.
The program control can be additionally influenced via P80:x bit 6
and bit 7.
Reserved
Control requested/no control requested
11
10
9
8
Reset the fault memory
Enable setpoint/inhibit setpoint
Ramp–function generator enable
Enable operation/disable operation
4 Communications via PROFIBUS–DP
4.2 Process data (PZD area)
If there is no function
Function available
Reserved
7
6
5
4
3
Operating condition/OFF 3
Operating condition/OFF 2
2
1
0
ON/OFF 1
4-107