Siemens SIMODRIVE POSMO A User Manual page 101

Distributed positioning motor on profibus dp
Hide thumbs Also See for SIMODRIVE POSMO A:
Table of Contents

Advertisement

4 Communications via PROFIBUS–DP
4.1 General information about PROFIBUS–DP
Data transfer
technology,
baud rate
Data transfer via
PROFIBUS
Essential
properties of bus
communications
Table 4-1
Essential properties of bus communications
Features
Supports 9.6 kbaud
Supports 19.2 kbaud
Supports 45.45 kbaud
Supports 93.75 kbaud
Supports 187.5 kbaud
Supports 500 kbaud
Supports 1.5 Mbaud
Supports 3 Mbaud
Supports 6 Mbaud
Supports 12 Mbaud
Supports the FREEZE control command
Supports the SYNC control command
Supports automatic baud rate search
Station number can be changed via software
Addressing
4-100
At power–up, the "DP slave POSMO A" automatically detects the baud
rate set on the fieldbus.
When commissioning the fieldbus, the baud rate is defined the same
for all devices starting from the master.
Data is transferred between the master and slaves according to the
master/slave principle. The drives are always the slaves.
This permits extremely fast cyclic data transfer.
For SIMODRIVE POSMO A for communications via PROFIBUS, the
following properties are involved:
The PROFIBUS node address and the terminating resistor are perma-
nently set in the connection cover of SIMODRIVE POSMO A.
––> Refer to Chapter 2.3.1
SIMODRIVE POSMO A User Manual (POS1) – 08/2013 Edition
Which of these does the "DP slave
POSMO A" have?
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
no
E Siemens AG 2013 All Rights Reserved
02.99

Advertisement

Table of Contents
loading

Table of Contents