02.99
08.06
04.01
P0701 / 2BD
Activate substitution
300W 075W
Min
Standard
0
0
The parameter is used to activate the telegram substitution function.
NOTICE:
The parameter acts i m m e d i a t e l y. After activation, the drive responds only to PZD control
signals, provided STW.10 = 1. Read b e f o r e using the parameter the further description in
the online help for SimoComA. (Menu: Help –> Short Introduction SimoComA –> Contents –>
Telegram substitution.)
P701=1
Telegram substitution activated
P701=0
Telegram substitution deactivated
Available from SW3.0 and higher.
P0702 / 2BE
Activate travel range adaptation
300W 075W
Min
Standard
0
0
In the case of large travel ranges, the travel range adaptation must be activated in order to
avoid inaccuracies.
To activate the travel range adaptation, the parameter must be set to value 1.
The change of parameter must be stored in the FEPROM of the drive (see P971), and a power
on reset must be executed.
If the travel range adaptation is active, parameter P703 shows value 1.
NOTICE:
Please read b e f o r e activation of the function the full description in the Online Help of Simo-
ComA. (Menu: Help –> Brief instructions SimoComA –> Menu-Button "index" –> traversing
range adaptation)
Note:
If the traversing range adaptation is active (compare P0704), the destination area will be deacti-
vated with the setting P0011 = 0.
Available from SW3.1 and higher.
P0703 / 2BE
current mode of travel range adaptation
300W 075W
Min
Standard
If the travel range adaptation is active, parameter P703 shows value 1.
NOTICE:
Please read b e f o r e activation of the function the full description in the Online Help of Simo-
ComA. (Menu: Help –> Brief instructions SimoComA –> Menu-Button "index" –> traversing
range adaptation).
Note:
If the traversing range adaptation is active (compare P0704), the destination area will be deacti-
vated with the setting P0011 = 0.
Available from SW3.1 and higher.
P0880 / 370
N-SETPOINT normalization
300W 075W
Min
Standard
–100000
4096
This parameter defines the normalization as to which speed sets in at the gear output when a
setpoint of 1000h (4096d) is specified via the control word (STW).
E Siemens AG 2013 All Rights Reserved
SIMODRIVE POSMO A User Manual (POS1) – 08/2013 Edition
5.6 Parameters for SIMODRIVE POSMO A
Max
Unit
1
Max
Unit
1
Max
Unit
Max
Unit
100000
rpm
5 Description of the Functions
Data type
Effective
I2
immed.
Data type
Effective
I2
PO
Data type
Effective
I2
RO
Data type
Effective
C4
immed.
5
5-225