4.1.18

REGEN SWITCH

The Regen Switch is used by the operator to initiate a parked regeneration. If "DPF J1939 Regen
SW Enable" is active, the CPC will no longer process the hardwired DPF Regen Switch requests.
The CPC must receive regular periodic switch status messages over J1939.
The Regen Switch is a momentary normally open switch. Refer to section 5.19 for additional
information.

Installation

The Regen Switch is wired to the CPC #4 connector pin 4/17. A switch is required or wiring
must be available to connect an external switch.

Programming Requirements and Flexibility

The options for this digital input are listed in Table 4-17.
Parameter
Parameter
Group
13
4 17 DI Selection
DPF J1939 Regen
46
Sw Enable
* Not supported in NAFTA
Table 4-17
Regen Switch Programming Options
All information subject to change without notice. (Rev. 01/07)
7SA827 0701 Copyright © 2007 DETROIT DIESEL CORPORATION
DDEC VI ELECTRONIC CONTROLS APPLICATION AND INSTALLATION
Options
0 – Disable
1 – 2 Clutch Switch*
2 – DPF Regeneration Switch
3 — FUSO Air Suspension Speed Limit
Switch*
0 – Not Active
1 – Active
Default
Access
2 – DPF
VEPS or
Regeneration
DRS
Switch
VEPS or
0 – Not Active
DRS
4-19