4.3.7
DPF REGENERATION LAMP (HARDWIRED AND J1939)
The purpose of this lamp is to let the operator know that a parked regeneration is required. This
lamp can be hardwired or multiplexed. Solid illumination indicates a manual regeneration is
required.
NOTE:
This function is optional.
Installation
This digital output circuit is designed to sink no more than 250 mA (DC) current.
The DPF Lamp is wired to pin 1/5 of the CPC.
Programming Requirements and Flexibility
The options for this digital output are listed in Table 4-33.
Parameter
Parameter
Group
1 05
35
DO Fault
Detection
DPF Lamp
46
Config
Table 4-33
DPF Regeneration Lamp Programming Options
All information subject to change without notice. (Rev. 01/07)
7SA827 0701 Copyright © 2007 DETROIT DIESEL CORPORATION
DDEC VI ELECTRONIC CONTROLS APPLICATION AND INSTALLATION
Setting
Options
0 – Disabled
—
1 – Enabled
0 – Hardwired
—
1 – J1939 PTC1
Default
Access
VEPS or
0 — Disabled
DRS
VEPS or
0 – Hardwired
DRS
4-35