NTP- D247 Provision External Alarms and Controls on the Alarm Interface Controller–International
Note
Complete the
Step 3
suppression and resume normal alarm reporting.
Stop. You have completed this procedure.
NTP-D247 Provision External Alarms and Controls on the Alarm
Interface Controller–International
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
For information about the AIC-I external alarms and controls, virtual wire, and orderwire, refer to the
Note
Cisco ONS 15454 SDH Reference Manual.
Verify the alarm contact wiring using the following substeps. See the
Step 1
Alarm, Timing, LAN, and Craft Pin Connections" procedure on page 1-15
ONS 15454 SDH contacts.
a.
b.
Step 2
Complete the
Step
Step 3
In the node view, double-click the AIC-I card shelf graphic. The card view appears.
Step 4
Click the Provisioning > Card tabs.
In the Input/Output area, click one of the following options:
Step 5
Cisco ONS 15454 SDH Procedure Guide, R7.0
9-8
Suppressing one or more alarms prevents them from appearing in Alarm or History windows or
in any other clients. The suppress command causes CTC to display them in the Conditions
window with their severity, their severity color code, and service-affecting status.
"DLP-D431 Discontinue Alarm Suppression" task on page 21-16
This procedure creates external (environmental) alarms and external
controls on the AIC or AIC-I card.
An AIC-I card must be installed in Slot 9.
NTP-D24 Verify Card Installation, page 4-2
As needed
Onsite or remote
Provisioning or higher
For external alarms, verify that the external device relays are wired to the ENVIR ALARMS IN
connector pins.
For external controls, verify the external device relays are wired to the ENVIR ALARMS OUT
connector pins.
"DLP-D60 Log into CTC" task on page
3.
External Alarm—Select External Alarm if you use external alarms only. Selecting External Alarm
gives you 20 external alarm ports.
External Control—Select External Control if you use both external alarms and external controls.
If you select External Control, four of the ports are converted to external control ports, leaving you
with 16 external alarm ports.
Chapter 9
"NTP-D223 Attach Wires to
for information about the
17-49. If you are already logged in, continue with
Manage Alarms
to discontinue alarm
78-17194-01