NTP- D342 Four-Fiber MS-SPRing Acceptance Test
After all tests are successfully completed and no alarms exist in the network, the network is ready for
service application. Continue with
Stop. You have completed this procedure.
NTP-D342 Four-Fiber MS-SPRing Acceptance Test
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
This procedure requires that you create test circuits and perform span switches around the ring. For
Note
clarity, "Node 1" refers to the login node where you begin the procedure. "Node 2" refers to the node
connected to the east STM-N trunk (span) card of Node 1, "Node 3" refers to the node connected to the
east STM-N trunk card of Node 2, and so on.
Complete the
Step 1
node will be called Node 1.) If you are already logged in, continue with Step 2.
From the View menu, choose Go to Network View.
Step 2
Click the Alarms tab.
Step 3
a.
b.
c.
Click the Conditions tab.
Step 4
a.
b.
On the network map, double-click Node 1.
Step 5
Complete the
Step 6
Complete the
Step 7
Create a test circuit between Node 1 and Node 2.
Step 8
Cisco ONS 15454 SDH Procedure Guide, R7.0
5-16
This procedure tests a four-fiber MS-SPRing.
Test set and cables appropriate to the test circuit you will create
NTP-D40 Provision MS-SPRing Nodes, page 5-10
NTP-D41 Create the MS-SPRing, page 5-13
As needed
Onsite
Provisioning or higher
"DLP-D60 Log into CTC" task on page 17-49
Verify that the alarm filter is not on. See the
page 19-25
as necessary.
Verify that no unexplained alarms appear on the network. If unexplained alarms appear, resolve
them before continuing. Refer to the Cisco ONS 15454 SDH Troubleshooting Guide if necessary.
Complete the
"DLP-D147 Export CTC Data" task on page 18-38
Verify that no unexplained conditions appear on the network. If unexplained conditions appear,
resolve them before continuing. Refer to the Cisco ONS 15454 SDH Troubleshooting Guide if
necessary.
Complete the
"DLP-D147 Export CTC Data" task on page 18-38
"DLP-D92 Four-Fiber MS-SPRing Exercise Span Test" task on page
"DLP-D217 MS-SPRing Exercise Ring Test" task on page
For VC4 circuits, complete the
procedure on page
6-55. When you set the circuit state, choose Unlocked and check the
Apply to drop ports check box.
Chapter 6, "Create Circuits and Low-Order Tunnels."
on the MS-SPRing you are testing. (This
"DLP-D227 Disable Alarm Filtering" task on
"NTP-D323 Create an Automatically Routed High-Order Circuit"
Chapter 5
Turn Up a Network
to export alarm information.
to export conditions information.
17-88.
19-15.