Technical Data

4.1 General Device Data

4.1
General Device Data

Analog Inputs

4.1.1
Current Inputs
Standard:
Nominal frequency
Frequency operating range (independent of the
nominal frequency)
Nominal current
Consumption per phase and ground path
- at Ι
= 1 A
N
- at Ι
= 5 A
N
Current overload capability
- thermal (rms)
- dynamic (peak value)
LoPo/LPS
1)
current inputs (via voltage values):
Rated voltage
Load capacity
- thermal (rms)
Input impedance
1)
For LoPo/LPS devices, to ensure the stated accuracy, you need to take one of the following actions:
Apply additional magnetic shielding measures to the devices.
Reduce the magnetic influence.
Voltage Inputs
Standard (also applies for LoPo/LPS and capacitive voltage measurement):
Nominal frequency
Frequency operating range (independent of the nominal
frequency)
Measuring range
Consumption
Voltage overload capability
- thermal (rms)
LoPo/LPS
1)
voltage inputs:
Secondary rated voltage
500
f
Nom
Ι
Nom
f
Nom
at 100 V
U
Nom
50 Hz or 60 Hz
25 Hz to 70 Hz
1 A or 5 A
For measured values of 10 mA or less there is a higher
tolerance (>10 %)
≤ 0.1 VA
≤ 0.5 VA
500 A for 1 s
150 A for 10 s
20 A continuous
1250 A (half-cycle)
200 mV to 20 V (max. 50 V RMS)
For measured values of 5 mV there is a
higher tolerance (>10 %)
200 V
100 V
40 kΩ
50 Hz or 60 Hz
(settable)
25 Hz to 70 Hz
200 mV to 250 V
For measured values of 25 mV or less there is a
higher tolerance (>10 %) compared to approx. 3 %
at 200 mV
approx. 0.005 VA
230 V continuous
0.5V to 40 V (parameterization)
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
(settable)
for 10 s
continuous