Siemens 7SC80 Manual page 629

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr. Parameter
711
EvLog Fill Lev2
712A
VT Assignment
1101
FullScaleVolt.
1102
FullScaleCurr.
1103
RE/RL
1104
XE/XL
1105
x'
1106
x'
1107
I MOTOR START
1108
P,Q sign
1109
Line angle
1110
Line length
1111
Line length
1201
FCT 50/51
1202
50-2 PICKUP
1203
50-2 DELAY
1204
50-1 PICKUP
1205
50-1 DELAY
1207
51 PICKUP
1208
51 TIME DIAL
1208
51 TIME DIAL
1209
51 TIME DIAL
1210
51 Drop-out
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Function
C
Setting Options
Device, General
10 .. 100 %
Device, General
6xPT
4xPT
P.System Data
0.10 .. 800.00 kV
2
P.System Data
10 .. 50000 A
2
P.System Data
-0.33 .. 7.00
2
P.System Data
-0.33 .. 7.00
2
P.System Data
1A
0.0050 ..
2
15.0000 Ω/mi
5A
0.0010 ..
3.0000 Ω/mi
P.System Data
1A
0.0050 ..
2
9.5000 Ω/km
5A
0.0010 ..
1.9000 Ω/km
P.System Data
1A
0.40 .. 10.00 A
2
5A
2.00 .. 50.00 A
P.System Data
not reversed
2
reversed
P.System Data
10 .. 89 °
2
P.System Data
0.1 .. 1000.0 km
2
P.System Data
0.1 .. 650.0 Miles
2
50/51 Overcur.
ON
OFF
50/51 Overcur. 1A
0.10 .. 30.00 A; ∞
5A
0.50 .. 150.00 A; ∞ 20.00 A
50/51 Overcur.
0.00 .. 7200.00 sec;
50/51 Overcur. 1A
0.10 .. 30.00 A; ∞
5A
0.50 .. 150.00 A; ∞ 5.00 A
50/51 Overcur.
0.00 .. 7200.00 sec;
50/51 Overcur. 1A
0.02 .. 4.00 A
5A
0.10 .. 20.00 A
50/51 Overcur.
0.05 .. 3.20 sec; ∞
50/51 Overcur.
0.01 .. 20.00 sec; ∞ 0.50 sec
50/51 Overcur.
0.50 .. 15.00 ; ∞
50/51 Overcur.
Instantaneous
Disk Emulation
Functions, Settings, Information
Default Setting
Comments
90 %
Threshold Fill level 2
Event Log
6xPT
VT Assignment
20.00 kV
Measurem:FullScale-
Voltage(Equipm.rating)
400 A
Measurem:FullScaleCur-
rent(Equipm.rating)
1.00
Zero seq. compensating
factor RE/RL
1.00
Zero seq. compensating
factor XE/XL
0.2420 Ω/mi
feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
feeder reactance per km:
x'
0.0300 Ω/km
2.50 A
Motor Start Current
(Block 49, Start 48)
12.50 A
not reversed
P,Q operational measured
values sign
85 °
Line angle
100.0 km
Line length in kilometer
62.1 Miles
Line length in miles
ON
50, 51 Phase Time Over-
current
4.00 A
50-2 Pickup
0.00 sec
50-2 Time Delay
1.00 A
50-1 Pickup
0.50 sec
50-1 Time Delay
1.00 A
51 Pickup
5.00 A
0.50 sec
51 Time Dial
51 Time Dial
5.00
51 Time Dial
Disk Emulation
Drop-out characteristic
F.2 Settings
629

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents