Functions, Settings, Information
F.2 Settings
Addr. Parameter
7400
Triple/Single
8001
START
8101
MEASURE. SUPERV Meas-
8102
BALANCE V-LIMIT
8103
BAL. FACTOR V
8104
BALANCE I LIMIT
8105
BAL. FACTOR I
8106
Σ I THRESHOLD
8107
Σ I FACTOR
8109
FAST Σ i MONIT
8201
FCT 74TC
8202
Alarm Delay
8301
DMD Interval
8302
DMD Sync.Time
8311
MinMax cycRESET
8312
MiMa RESET TIME
8313
MiMa RESETCYCLE Min/Max meter
8314
MinMaxRES.START Min/Max meter
8315
MeterResolution
9501
FCT Sec.
9502
Sec. CLP Det.
692
Function
C
Setting Options
Triple Single
3PTrip-3PLO
1PTrip-3PLO
1PTrip-1PLO
Fault Locator
Pickup
TRIP
OFF
urem.Superv
ON
Meas-
10 .. 100 V
urem.Superv
Meas-
0.58 .. 0.90
urem.Superv
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
0.10 .. 0.90
urem.Superv
Meas-
1A
0.05 .. 2.00 A; ∞
urem.Superv
5A
0.25 .. 10.00 A; ∞
Meas-
0.00 .. 0.95
urem.Superv
Meas-
OFF
urem.Superv
ON
74TC TripCirc.
ON
OFF
74TC TripCirc.
1 .. 30 sec
Demand meter
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
Demand meter
On The Hour
15 After Hour
30 After Hour
45 After Hour
Min/Max meter
NO
YES
Min/Max meter
0 .. 1439 min
1 .. 365 Days
1 .. 365 Days
Energy
Standard
Factor 10
Factor 100
Sectionalizer
OFF
ON
Sectionalizer
OFF
ON
Default Setting
Comments
3PTrip-3PLO
Triple/Single Mode
Pickup
Start fault locator with
ON
Measurement Supervision
50 V
Voltage Threshold for
Balance Monitoring
0.75
Balance Factor for
Voltage Monitor
0.50 A
Current Threshold for
Balance Monitoring
2.50 A
0.50
Balance Factor for Current
Monitor
0.10 A
Summated Current Moni-
toring Threshold
0.50 A
0.10
Summated Current Moni-
toring Factor
ON
Fast Summated Current
Monitoring
ON
74TC TRIP Circuit Supervi-
sion
2 sec
Delay Time for alarm
60 Min., 1 Sub
Demand Calculation Inter-
vals
On The Hour
Demand Synchronization
Time
YES
Automatic Cyclic Reset
Function
0 min
MinMax Reset Timer
7 Days
MinMax Reset Cycle
Period
1 Days
MinMax Start Reset Cycle
in
Standard
Meter resolution
OFF
Sectionalizer Function
OFF
Sec. Cold Load Pickup
Detection
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017