Thermal Overload Protection 49
Thermal profile of energy losses (overload protection has full memory capability)
True RMS calculation
Adjustable thermal warning element
Adjustable alarm level based on current magnitude
Additional time constant setting for motors to accommodate the motor at standstill
Monitoring Functions
Increased reliability due to monitoring of the internal measurement circuits as well as the hardware and
software
Voltage transformer monitoring with protection function blocking
Broken conductor detection
Monitoring of the current transformer and voltage transformer secondary circuits using sum and
symmetry supervision with optional protection function blocking
Inrush current detection with 2nd harmonic for directional and non-directional overcurrent protection
Phase rotation check.
Ground Fault Detection 50N(s), 51N(s), 67N(s), 59N/64
Displacement voltage is measured or calculated from the three phase voltages
Determination of a faulty phase on ungrounded or grounded systems
Two element ground fault detection: 50Ns-1 and 50Ns-2
High sensitivity (as low as 1 mA)
Overcurrent element with definite time or inverse time delay
For inverse time overcurrent protection, characteristics according to IEC or ANSI standards and a userde-
fined characteristic are available
Direction determination with zero-sequence quantities (I0, V0), watt-metric ground fault direction deter-
mination
Sector characteristic settable as directional characteristic
Any elementcan be set as directional or non-directional — forward sensing directional or reverse sensing
directional
Optionally applicable as additional ground fault protection
Automatic Reclosing 79
Single-shot or multi-shot
With separate dead times for the first three and all subsequent shots
You can configure which of the overcurrent protection elements work with automatic reclosing and
which not
Separate programs for phase and ground faults
Interaction with the time overcurrent protection elements. These can be blocked depending on the
reclosing cycle or trip instantaneously.
Sectionalizer
Have no capacity to break the fault current
Isolate the fault current sections of a distribution circuit only when an upstream breaker or recloser has
interrupted the fault current.