Siemens 7SC80 Manual page 406

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.29 Recloser Setting Summary
Special Parameters in
Easy Setting GUI View
Trip #3 Phase Curve
Trip #3 Ground Curve
Phase Reclose Interval
3
Ground Reclose
Interval 3
Trip #4 Phase Curve
Trip #4 Ground Curve
Phase Reclose Interval
4
Ground Reclose
Interval 4
Reclose Reset Time
406
C
Setting Options
Fast Curve x
Delayed Curve x
Fast Curve y
Delayed Curve y
Fast Curve x
Delayed Curve x
Fast Curve y
Delayed Curve y
0.01 .. 320.00 sec
0.01 .. 320.00 sec
Fast Curve x
Delayed Curve x
Fast Curve y
Delayed Curve y
Fast Curve x
Delayed Curve x
Fast Curve y
Delayed Curve y
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.50 .. 320.00 sec
Default Setting Description
Fast Curve x
Select a fast or delayed
curve for the 3rd phase
overcurrent trip.
Fast Curve x
Select a fast or delayed
curve for the 3rd
ground overcurrent
trip.
0.50 sec
This setting will determine
the reclose interval time in
the 3rd phase
reclose cycle.
0.50 sec
This setting will determine
the reclose interval time in
the 3rd ground
reclose cycle.
Fast Curve x
Select a fast or delayed
curve for the 4th phase
overcurrent trip.
Fast Curve x
Select a fast or delayed
curve for the 4th
ground overcurrent
trip.
0.50 sec
This setting will determine
the reclose interval
time in the 4th phase
reclose cycle.
0.50 sec
This setting will determine
the reclose interval time in
the 4th ground
reclose cycle.
3.00 sec
This setting will determine
the elapsed time after a
successful reclosing
attempt.If no new trip
provokes when the time
expires, the automatic
reclosure would be reset.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017