The following must be observed:
The value pairs should be entered in increasing sequence. If desired, fewer than 20 pairs can be entered.
In most cases, about 10 pairs is sufficient to define the characteristic accurately. A value pair which will
not be used has to be made invalid by entering "∞" for the threshold! The user must ensure that the value
pairs produce a clear and constant characteristic
The current values entered should be those from
values Ι/Ι
are rounded. This, however, will not be indicated.
p
Current below the current value of the smallest curve point will not lead to an extension of the tripping
time. The pickup curve (see
axis.
Current flows greater than the highest current value entered will not result in a reduced tripping time.
The pickup curve (see
Table 2-17
MofPU = 1 bis 1.94
1.00
1.50
1.06
1.56
1.13
1.63
1.19
1.69
1.25
1.75
1.31
1.81
1.38
1.88
1.44
1.94
[verwendung-einer-anwenderspezifizierbaren-kennlinie-260602-kn, 1, en_US]
Figure 2-94
Determination of Ground-faulted Phase
The phase connected to ground may be identified in an ungrounded or resonant grounded system, if the
device is supplied by three voltage transformers connected in a grounded-wye configuration or the phase-to-
ground voltages are calculated. The phase in which the voltage lies below setting VPH MIN (address 3106) is
identified as the faulty phase as long as the other two phase voltages simultaneously exceed setting VPH MAX
(address 3107). The setting VPH MIN must be set to less than the minimum expected operational phase-to-
ground voltage. A typical setting for this address would be 40 V. Setting VPH MAX must be greater than the
maximum expected operational phase-to-ground voltage, but less than the minimum expected operational
phase-to-phase voltage. For V
significance in a grounded system.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Figure
2-94) continues, from the smallest current point parallel to the current
Figure
2-94) continues, from the highest current point parallel to the current axis.
Preferential Values of Standardized Currents for User-specific Tripping Curves
MofPU = 2 bis 4.75
2.00
3.50
2.25
3.75
2.50
4.00
2.75
4.25
3.00
4.50
3.25
4.75
Use of a user-defined characteristic
= 100 V, approximately 75 V is a typical setting. These settings have no
Nom
2.13 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
Table
2-5, along with the matching times. Deviating
MofPU = 5 bis 7.75
5.00
6.50
5.25
6.75
5.50
7.00
5.75
7.25
6.00
7.50
6.25
7.75
Functions
MofPU = 8 bis 20
8.00
15.00
9.00
16.00
10.00
17.00
11.00
18.00
12.00
19.00
13.00
20.00
14.00