Siemens 7SC80 Manual page 647

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr. Parameter
1611
67N-TOC IEC
1612
67N-TOC ANSI
1613A MANUAL CLOSE
1614A 67N-2 active
1617
67N POLARIZAT.
1618A 67N T DROP-OUT
1619A ROTATION ANGLE
1620A 67N-2 MEASUREM. 67 Direct. O/C
1621A 67N-1 MEASUREM. 67 Direct. O/C
1622A 67N-TOC MEASUR. 67 Direct. O/C
1623
67N-2 Direction
1624
67N-1 Direction
1625
67N-TOC Direct.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Function
C
Setting Options
67 Direct. O/C
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
67 Direct. O/C
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
67 Direct. O/C
67N-3 instant.
67N-2 instant.
67N-1 instant.
67N-TOC instant
67N-TOC-1 inst.
67N-TOC-2 inst.
67N-TOC-3 inst.
67N-TOC-4 inst.
Inactive
67 Direct. O/C
always
with 79 active
67 Direct. O/C
with VN and IN
with V2 and I2
67 Direct. O/C
0.00 .. 60.00 sec
67 Direct. O/C
-180 .. 180 °
Fundamental
True RMS
Fundamental
True RMS
Fundamental
True RMS
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
Forward
Reverse
Non-Directional
Functions, Settings, Information
Default Setting
Comments
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
67N-3 instant.
Manual Close Mode
always
67N-2 active
with VN and IN
Ground Polarization
0.00 sec
67N Drop-Out Time Delay
-45 °
Rotation Angle of Refer-
ence Voltage
Fundamental
67N-2 measurement of
Fundamental
67N-1 measurement of
Fundamental
67N-TOC measurement
of
Forward
67N-2 Direction
Forward
67N-1 Direction
Forward
67N-TOC Direction
F.2 Settings
647

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents