Siemens 7SC80 Manual page 28

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Introduction
1.3 Characteristics
Direction determination with cross-polarized voltages and voltage memory and dynamically unlimited
direction sensitivity
Fault direction is calculated phase-selectively and separately for phase faults, ground faults and summa-
tion current faults.
Dynamic Cold Load Pick-up Function 50C, 50NC, 51C, 51NC, 67C, 67NC
Dynamic changeover of time overcurrent protection settings, e.g. when cold load conditions are recog-
nized
Detection of cold load condition via circuit breaker position or current threshold
Activation via automatic reclosure (AR) is possible
Activation also possible via binary input.
Single-Phase Overcurrent Protection
Evaluation of the measured current via the sensitive ground current transformer
Suitable as differential protection that includes the neutral point current on transformer side, generator
side, or motor side or for a grounded reactor set
As tank leakage protection against abnormal leakage currents between transformer tanks and ground
Voltage Protection
Two element undervoltage detection via the positive-sequence system of the voltages, phase-to-phase or
phase-to-ground voltages
Phase-specific undervoltage detection
Choice of current supervision for 27-1 and 27-2
Separate two element overvoltage detection of the largest applied voltages or detection of the positive-
sequence component of the voltages
Phase-specific overvoltage detection
Settable dropout ratio for all elements of the undervoltage and overvoltage protection
Residual-voltage protection
Negative-Sequence System Overvoltage Protection
Detection of the negative-sequence component of the voltages
Voltage Protection for Vx
Two element undervoltage and overvoltage protection for 1-phase voltage connection to Vx
Settable dropout ratio for all elements of the single-phase undervoltage and overvoltage protection Vx.
Negative Sequence Protection 46
Evaluation of the negative sequence component of the currents
Two definite-time elements 46-1 and 46-2 and one inverse-time element 46-TOC; curves of common
standards are available for 46-TOC.
Frequency Protection
Monitoring of falling below (f<) and/or exceeding (f>) with 4 frequency limits and time delays that are
independently adjustable
Insensitive to harmonics and abrupt phase angle changes
Adjustable undervoltage threshold.
28
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017