Settings; Information List - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.21 Capacitor Control
The capacitor bank control does not require feedback inputs from the capacitor bank. The ON and OFF
commands are monitored internally by the RS flip-flop, which provides the feedback outputs 2544
Status ON and 2545 CapCmdStat. OFF to the control center and the rest of the system. In order to
synchronize the internal feedback with the actual capacitor bank status, 7SC80 issues one single OFF
command when initialized for the first time. The input 2558
permanent high indication. If the application employs the 7SC80 capacitor bank control function, any other
existing controllers should be disabled to avoid duplicate or opposite commands to the capacitor bank.
More indications can be found in the following information overview.

Settings

2.21.3
Addr.
Parameter
1240
Capacitor Ctrl.
1241
T Startup
1242
TD ON Command
1243
T ON/OFF CMD
2.21.4

Information List

No.
Information
2542
ON CMD
2543
OFF CMD
2544
CapCmdStatus ON
2545
CapCmdStat. OFF
2554
Cap Imbal. Trip
2555
En Man.Operat.
2556
ON CMD ManOper.
2557
OFF CMD ManOper
2558
Init OFF Enable
2559
AUTO Mode ON
2560
ON CMD Auto
2561
OFF CMD Auto
2562
27 Pickup
2563
Stand-aloneOper
2564
59 Pickup
2565
SimMode ON
350
Setting Options
OFF
ON
0.00 .. 3600.00 sec
0.0 .. 60.0 min
0.00 .. 900.00 sec
Type of
Comments
Informa-
tion
OUT
ON Command
OUT
OFF Command
OUT
Capacitor control command status ON
OUT
Capacitor control command status OFF
SP
Capacitor Control Imbalance TRIP
SP
Enable Manual Operation
SP
ON Command Manual Operation
SP
OFF Command Manual Operation
SP
Initialization OFF Enable
SP
Automatic Mode On
SP
ON Command Automatic mode
SP
OFF Command Automatic mode
SP
27 Undervoltage pickup
SP
Stand-alone Operation
SP
59 Overvoltage pickup
SP
Simulation Mode ON
Init OFF Enable should be provided with a
Default Setting
Comments
OFF
Capacitor Control
5.00 sec
Startup Time Device
1.0 min
ON command delay time
10.00 sec
ON/OFF command time
SIPROTEC Compact, 7SC80, Manual