Siemens 7SC80 Manual page 670

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
5703
27-1 PICKUP S2
5704
27-1 DELAY S2
5705
27-2 PICKUP S2
5706
27-2 PICKUP S2
5707
27-2 DELAY S2
5708A 27-1 DOUT S2
5709A 27-2 DOUT S2
5710A CURRENT SUPERV.
5712
27-1Ph2A Pickup
5713
27-1Ph2A Pickup
5714
27-1Ph2B Pickup
5715
27-1Ph2B Pickup
5716
27-1Ph2C Pickup
5717
27-1Ph2C Pickup
5718
27-2Ph2A Pickup
5719
27-2Ph2A Pickup
5720
27-2Ph2B Pickup
5721
27-2Ph2B Pickup
5722
27-2Ph2C Pickup
5723
27-2Ph2C Pickup
5724
27-1 Ph2A Delay
5725
27-1 Ph2B Delay
5726
27-1 Ph2C Delay
5727
27-2 Ph2A Delay
5728
27-2 Ph2B Delay
5729
27-2 Ph2C Delay
5901
FCT 81 O/U S2
5902
Vmin S2
5903
FCT 81-1 O/U S2
5904
FCT 81-2 O/U S2
5905
FCT 81-3 O/U S2
670
Function
C
Setting Options
27/59 S2
10 .. 120 V
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
10 .. 210 V
27/59 S2
10 .. 120 V
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
1.01 .. 3.00
27/59 S2
1.01 .. 3.00
27/59 S2
OFF
ON
27/59 S2
10 .. 210 V
27/59 S2
10 .. 120 V
27/59 S2
10 .. 210 V
27/59 S2
10 .. 120 V
27/59 S2
10 .. 210 V
27/59 S2
10 .. 120 V
27/59 S2
10 .. 210 V
27/59 S2
10 .. 120 V
27/59 S2
10 .. 210 V
27/59 S2
10 .. 120 V
27/59 S2
10 .. 210 V
27/59 S2
10 .. 120 V
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
81 O/U Freq.S2
OFF
ON
81 O/U Freq.S2
10 .. 150 V
81 O/U Freq.S2
OFF
ON f>
ON f<
81 O/U Freq.S2
OFF
ON f>
ON f<
81 O/U Freq.S2
OFF
ON f>
ON f<
Default Setting
Comments
45 V
27-1 Pickup Side2
1.50 sec
27-1 Time Delay Side2
70 V
27-2 Pickup Side2
40 V
27-2 Pickup Side2
0.50 sec
27-2 Time Delay Side2
1.20
27-1 Dropout Ratio Side2
1.20
27-2 Dropout Ratio Side2
OFF
Current Supervision
75 V
27-1 Phase 2A Pickup
45 V
27-1 Phase 2A Pickup
75 V
27-1 Phase 2B Pickup
45 V
27-1 Phase 2B Pickup
75 V
27-1 Phase 2C Pickup
45 V
27-1 Phase 2C Pickup
70 V
27-2 Phase 2A Pickup
40 V
27-2 Phase 2A Pickup
70 V
27-2 Phase 2B Pickup
40 V
27-2 Phase 2B Pickup
70 V
27-2 Phase 2C Pickup
40 V
27-2 Phase 2C Pickup
1.50 sec
27-1 Phase 2A Time Delay
1.50 sec
27-1 Phase 2B Time Delay
1.50 sec
27-1 Phase 2C Time Delay
0.50 sec
27-2 Phase 2A Time Delay
0.50 sec
27-2 Phase 2B Time Delay
0.50 sec
27-2 Phase 2C Time Delay
OFF
81 Over/Under Frequency
Prot. Side2
65 V
Min.required volt.for
operation Side2
OFF
81-1 Over/Under
Frequency Prot. Side2
OFF
81-2 Over/Under
Frequency Prot. Side2
OFF
81-3 Over/Under
Frequency Prot. Side2
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links:

Advertisement

Table of Contents
loading