Siemens 7SC80 Manual page 668

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
5501
46BC
5502
T 46BC
5503
Curr. Factor BC
5504
Volt. Factor BC
5505
CT Location
5506
VT Location
5510
60VTS
5511
60VTS V2
5512
60VTS V0
5513
60VTS I2
5514
60VTS I0
5515
60VTS I1 load
5516
60VTS I1 fault
5517
60VTS V1
5518
60VTS T-Delay
5520
60CTS
5521
60CTS V2
5522
60CTS I2
5523
60CTS T-Delay
5530
60VTS S2
5531
60VTS V2 S2
5532
60VTS I2 S2
5533
60VTS I1 loadS2
5534
60VTS I1 flt S2
668
Function
C
Setting Options
Meas-
OFF
urem.Superv
ON
Meas-
0.00 .. 100.00 sec
urem.Superv
Meas-
0.00 .. 1.00
urem.Superv
Meas-
0.00 .. 1.00
urem.Superv
Meas-
Direction 1
urem.Superv
Direction 2
Meas-
Direction 1
urem.Superv
Direction 2
Meas-
OFF
urem.Superv
ON with NPS
Meas-
7 .. 110 V
urem.Superv
Meas-
7 .. 110 V
urem.Superv
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
1A
0.10 .. 10.00 A
urem.Superv
5A
0.50 .. 50.00 A
Meas-
1 .. 110 V
urem.Superv
Meas-
0.03 .. 320.00 sec
urem.Superv
Meas-
OFF
urem.Superv
ON
Meas-
7 .. 110 V
urem.Superv
Meas-
1A
0.04 .. 1.00 A
urem.Superv
5A
0.20 .. 5.00 A
Meas-
0.03 .. 320.00 sec
urem.Superv
Meas-
OFF
urem.Superv
ON with NPS
Meas-
7 .. 110 V
urem.Superv
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
1A
0.10 .. 10.00 A
urem.Superv
5A
0.50 .. 50.00 A
Default Setting
Comments
OFF
46 Broken Conductor
2.00 sec
46BC Delay Time
0.10
Current Factor for Broken
Conductor
0.10
Voltage Factor for Broken
Conductor
Direction 1
Measurement location of
CT
Direction 1
Measurement location of
VT
OFF
60VTS Voltage Trans-
former Supervision
7 V
60VTS Threshold V2
7 V
60VTS Threshold V0
0.10 A
60VTS Threshold I2
0.50 A
0.10 A
60VTS Threshold I0
0.50 A
0.10 A
60VTS Threshold I1 load
0.50 A
10.00 A
60VTS Threshold I1 fault
50.00 A
15 V
60VTS Threshold V1
10.00 sec
60VTS Time Delay
OFF
60CTS Current Trans-
former Supervision
7 V
60CTS Threshold V2
0.04 A
60CTS Threshold I2
0.20 A
10.00 sec
60CTS Time Delay
OFF
60VTS Voltage
Transf.Superv.Side2
7 V
60VTS Threshold V2
Side2
0.10 A
60VTS Threshold I2 Side2
0.50 A
0.10 A
60VTS Threshold I1 load
Side2
0.50 A
10.00 A
60VTS Threshold I1 fault
Side2
50.00 A
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017