[verriegelungsbeding-20110912, 1, en_US]
Figure 2-129
With the Web Monitor, configured interlocking causes are output on the device display. They are marked by
letters explained in the following table.
Table 2-27
Interlocking Commands
Switching Authority
System interlocking
Zone controlled
SET = ACTUAL (switch direction check)
Protection blocking
Control Logic using CFC
For bay interlocking, a release logic can be created using CFC. Via specific release conditions the information
"released" or "bay interlocked" are available (e.g. object "52 Close" and "52 Open" with the data values: ON/
OFF).
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
DIGSI dialog box 'Object properties' for setting the interlocking conditions
Command types and corresponding messages