Information List; Voltage-Transformer Supervision Of Side 2; Description - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.30 Additional Applications with 6 Voltage Inputs
Addr.
Parameter
5907A
DO differential
5908
81-1 PICKUP S2
5909
81-1 PICKUP S2
5910
81-1 DELAY S2
5911
81-2 PICKUP S2
5912
81-2 PICKUP S2
5913
81-2 DELAY S2
5914
81-3 PICKUP S2
5915
81-3 PICKUP S2
5916
81-3 DELAY S2
5917
81-4 PICKUP S2
5918
81-4 PICKUP S2
5919
81-4 DELAY S2
2.30.3.4

Information List

No.
Information
31316
>BLK 81 O/U S2
31317
>BLK 81-1 S2
31318
>BLK 81-2 S2
31319
>BLK 81-3 S2
31320
>BLK 81-4 S2
31321
81 OFF S2
31322
81 BLOCKED S2
31323
81 ACTIVE S2
31324
81 UV Blk S2
31325
81-1 PU S2
31326
81-2 PU S2
31327
81-3 PU S2
31328
81-4 PU S2
31329
81-1 TRIP S2
31330
81-2 TRIP S2
31331
81-3 TRIP S2
31332
81-4 TRIP S2

Voltage-Transformer Supervision of Side 2

2.30.4
2.30.4.1

Description

General
In practice, voltage-transformer faults occur rather rarely. More frequently, it is the fuses connected in series
to the voltage transformers which fail. Such a failure is detected by the voltage transformer supervision func-
tion and signaled with a warning indication. 1-, 2-, and 3-phase faults are detected.
The limit values and delay times for the function can be parameterized.
442
Setting Options
0.04 .. 1.00 Hz
40.00 .. 60.00 Hz
50.00 .. 70.00 Hz
0.00 .. 100.00 sec; ∞
40.00 .. 60.00 Hz
50.00 .. 70.00 Hz
0.00 .. 100.00 sec; ∞
40.00 .. 60.00 Hz
50.00 .. 70.00 Hz
0.00 .. 100.00 sec; ∞
40.00 .. 60.00 Hz
50.00 .. 70.00 Hz
0.00 .. 100.00 sec; ∞
Type of
Comments
Informa-
tion
SP
>BLOCK 81O/U Side2
SP
>BLOCK 81-1 Side2
SP
>BLOCK 81-2 Side2
SP
>BLOCK 81-3 Side2
SP
>BLOCK 81-4 Side2
OUT
81 OFF Side2
OUT
81 BLOCKED Side2
OUT
81 ACTIVE Side2
OUT
81 Under Voltage Block Side2
OUT
81-1 picked up Side2
OUT
81-2 picked up Side2
OUT
81-3 picked up Side2
OUT
81-4 picked up Side2
OUT
81-1 TRIP Side2
OUT
81-2 TRIP Side2
OUT
81-3 TRIP Side2
OUT
81-4 TRIP Side2
Default Setting
Comments
0.04 Hz
Dropout differential
49.50 Hz
81-1 Pickup Side2
59.50 Hz
81-1 Pickup Side2
60.00 sec
81-1 Time Delay Side2
49.00 Hz
81-2 Pickup Side2
59.00 Hz
81-2 Pickup Side2
30.00 sec
81-2 Time Delay Side2
47.50 Hz
81-3 Pickup Side2
57.50 Hz
81-3 Pickup Side2
3.00 sec
81-3 Time delay Side2
51.00 Hz
81-4 Pickup Side2
61.00 Hz
81-4 Pickup Side2
30.00 sec
81-4 Time delay Side2
SIPROTEC Compact, 7SC80, Manual