Special Parameters in
Easy Setting GUI View
Close Wait Time
Minimum Trip Fast
Curve x Phase
Minimum Trip Fast
Curve x Ground
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
0.10 .. 320.00 sec
1 A
0.10 .. 4.00 A; ∞
5 A
0.50 .. 20.00 A; ∞
1 A
0.05 .. 4.00 A; ∞
5 A
0.25 .. 20.00 A; ∞
2.29 Recloser Setting Summary
Default Setting Description
3.00 sec
If the circuit breaker
turns to not ready,
set the Close Wait
Time to define the
max-allowed time for
the circuit breaker to
recover to normal.
If the circuit breaker
is not ready when the
time expires, the
reclosing would be
omitted, the auto-
matic reclosure
would be dynami-
cally blocked.
Only if Circuit Breaker
Check before AR is acti-
vated, the Close Wait
Time parameter is valid.
1.00 A
Set the minimum trip
values for the Fast
5.00 A
curve x phase.
0.20 A
Set the minimum trip
values for the Fast
1.00 A
curve x ground.