Monitoring
Working memory ROM
Program memory RAM
Parameter memory
Sampling frequency
Error in the I/O board
Error in the extension I/O
board
Offset monitoring
Current sum
Current symmetry
Voltage symmetry
Voltage phase sequence
Current phase sequence
Voltage transformer moni-
toring
Adjustment data error
1)
Following three unsuccessful restarting attempts, the device is put out of operation.
2)
DOK = "Device OK" = readiness relay drops out; protection and control functions are blocked.
3)
There is a separate power supply for extension I/O board.
Group Indications
Certain indications of the monitoring functions are already combined to group indications. These group indica-
tions and their composition are stated in the Appendix
Alarm Sum Event is only issued when the measured value monitoring functions (8101 MEASURE.
SUPERV) are activated.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Possible causes
Malfunction response Indication (No.)
internal
Abortion of restart,
device shutdown
(hardware)
internal
During boot sequence LED "ERROR"
(hardware)
During operation:
Device out of service
internal
Device out of service
(hardware)
internal
Device shutdown
(hardware)
internal
Device shutdown
(hardware)
internal
Device shutdown
(hardware)
external
(power supply for
extension I/O board)
3)
internal
Device shutdown
(hardware)
internal
Indication
(measured value
acquisition)
external
Indication
(system or current
transformer)
external
Indication
(system or voltage
transformer)
external
Indication
(system or connec-
tion)
external
Indication
(system or connec-
tion)
external
Indication
(voltage transformer)
internal
Indication
(hardware)
LED blinkt
LED "ERROR"
1)
LED "ERROR"
1)
LED "ERROR"
I/O-Board error
(178),
LED "ERROR"
Error Ext. I/O
(10080),
LED "ERROR"
Error Offset (191) DOK
Failure Σ I (162)
Fail I balance
(163)
Fail V balance
(167)
Fail Ph. Seq. V
176)
Fail Ph. Seq. I
(175)
Fail VT Superv.
(170)
Alarm NO calibr
(193)
F.4 Group
Alarms. Keep in mind that the indication 160
Functions
2.12 Monitoring Functions
Output
DOK
2)
drops
out
DOK
2)
drops
out
DOK
2)
drops
out
DOK
2)
drops
out
DOK
2)
drops
out
DOK
2)
drops
out
2)
drops
out
as allocated
as allocated
as allocated
as allocated
as allocated
as allocated
as allocated
247