Information List - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr.
Parameter
2214
51N w. Inrush
2221
51-1 w. Inrush
2222
51-2 w. Inrush
2223
51-3 w. Inrush
2224
51-4 w. Inrush
2226
51N-1 w. Inrush
2227
51N-2 w. Inrush
2228
51N-3 w. Inrush
2229
51N-4 w. Inrush

Information List

2.2.14
No.
Information
1704
>BLK 50/51
1714
>BLK 50N/51N
1718
>BLOCK 50-3
1719
>BLOCK 50N-3
1721
>BLOCK 50-2
1722
>BLOCK 50-1
1723
>BLOCK 51
1724
>BLOCK 50N-2
1725
>BLOCK 50N-1
1726
>BLOCK 51N
1751
50/51 PH OFF
1752
50/51 PH BLK
1753
50/51 PH ACT
1756
50N/51N OFF
1757
50N/51N BLK
1758
50N/51N ACT
1761
50(N)/51(N) PU
1762
50/51 Ph A PU
1763
50/51 Ph B PU
1764
50/51 Ph C PU
1765
50N/51NPickedup
1767
50-3 picked up
1768
50N-3 picked up
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
Type of
Comments
Informa-
tion
SP
>BLOCK 50/51
SP
>BLOCK 50N/51N
SP
>BLOCK 50-3
SP
>BLOCK 50N-3
SP
>BLOCK 50-2
SP
>BLOCK 50-1
SP
>BLOCK 51
SP
>BLOCK 50N-2
SP
>BLOCK 50N-1
SP
>BLOCK 51N
OUT
50/51 O/C switched OFF
OUT
50/51 O/C is BLOCKED
OUT
50/51 O/C is ACTIVE
OUT
50N/51N is OFF
OUT
50N/51N is BLOCKED
OUT
50N/51N is ACTIVE
OUT
50(N)/51(N) O/C PICKUP
OUT
50/51 Phase A picked up
OUT
50/51 Phase B picked up
OUT
50/51 Phase C picked up
OUT
50N/51N picked up
OUT
50-3 picked up
OUT
50N-3 picked up
2.2 Overcurrent Protection 50, 51, 50N, 51N
Default Setting
Comments
NO
51N with Inrush Restraint
NO
51-1 with Inrush Restraint
NO
51-2 with Inrush Restraint
NO
51-3 with Inrush Restraint
NO
51-4 with Inrush Restraint
NO
51N-1 with Inrush Restraint
NO
51N-2 with Inrush Restraint
NO
51N-3 with Inrush Restraint
NO
51N-4 with Inrush Restraint
Functions
107

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents