Communication Interfaces - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Communication Interfaces

4.1.4
User Interface
Connection
Operation
Transmission speed
Bridgeable distance
Port F
DNP3.0
Terminal
Test voltage
Transmission speed
Bridgeable distance
Ethernet electrical (EN 100) for IEC61850, DNP3 TCP, PROFINET, IEC60870-5-104 and DIGSI
Connection
Line
Test voltage (for socket)
Transmission speed
Maximum distance of transmission
Ethernet optical (EN 100 O SM or mulitmode) for IEC61850, DNP3 TCP, PROFINET, IEC60870-5-104 and
DIGSI
Connection
Transmission speed
Fiber types
Permissible bending radii
Maximum distance of transmission
Transmitter
Optical wavelength λc
Output power P
Receiver
Sensitivity P
Min
IN
Overload P
Max
IN
GPS Connection
Connection
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
OUT
At the front, non-isolated, USB type B socket for connecting a
personal computer
Operation for DIGSI V4.85 and higher versions via USB 2.0 full
speed
with DIGSI
up to 12 Mbit/s max.
5 m
Back case bottom, mounting location "B", 9 pin DSUB socket
500 V; 50 Hz
Up to 57,600 Bd
max. 1 km
2 x RJ45 socket
100 BaseT acc. to IEEE802.3
CAT 5 (twisted and screened in pairs)
500 V; 50 Hz
100 MBit/s
20 m
Duplex-LC, 100BaseF in acc. with IEEE802.3
100 MBit/s
Singlemode optical fiber G9 μm/125 μm
Multimode optical fiber G50 μm/125 μm, G62,5μm/125 μm
for indoor cable r
= 5 cm
min
for outdoor cable r
= 20 cm
min
max. 24 km for singlemode
1270 nm to 1360 nm
-15 dBm to -8 dBm
min. -31 dBm
max. -8 dBm
SMB socket (subminiature B) at device
Active GPS antenna
5 V, max. 50 mA
Technical Data