Information List - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr.
Parameter
5511
60VTS V2
5512
60VTS V0
5513
60VTS I2
5514
60VTS I0
5515
60VTS I1 load
5516
60VTS I1 fault
5517
60VTS V1
5518
60VTS T-Delay
5520
60CTS
5521
60CTS V2
5522
60CTS I2
5523
60CTS T-Delay
8101
MEASURE. SUPERV
8102
BALANCE V-LIMIT
8103
BAL. FACTOR V
8104
BALANCE I LIMIT
8105
BAL. FACTOR I
8106
Σ I THRESHOLD
8107
Σ I FACTOR
8109
FAST Σ i MONIT
2.12.1.10

Information List

No.
Information
161
Fail I Superv.
162
Failure Σ I
163
Fail I balance
167
Fail V balance
170
Fail VT Superv.
171
Fail Ph. Seq.
175
Fail Ph. Seq. I
176
Fail Ph. Seq. V
197
MeasSup OFF
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
7 .. 110 V
7 .. 110 V
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
1A
0.10 .. 10.00 A
5A
0.50 .. 50.00 A
1 .. 110 V
0.03 .. 320.00 sec
OFF
ON
7 .. 110 V
1A
0.04 .. 1.00 A
5A
0.20 .. 5.00 A
0.03 .. 320.00 sec
OFF
ON
10 .. 100 V
0.58 .. 0.90
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
0.10 .. 0.90
1A
0.05 .. 2.00 A; ∞
5A
0.25 .. 10.00 A; ∞
0.00 .. 0.95
OFF
ON
Type of
Comments
Informa-
tion
OUT
Failure: General Current Supervision
OUT
Failure: Current Summation
OUT
Failure: Current Balance
OUT
Failure: Voltage Balance
OUT
Failure: VT Supervision (alarm instant.)
OUT
Failure: Phase Sequence
OUT
Failure: Phase Sequence Current
OUT
Failure: Phase Sequence Voltage
OUT
Measurement Supervision is switched OFF
2.12 Monitoring Functions
Default Setting
Comments
7 V
60VTS Threshold V2
7 V
60VTS Threshold V0
0.10 A
60VTS Threshold I2
0.50 A
0.10 A
60VTS Threshold I0
0.50 A
0.10 A
60VTS Threshold I1 load
0.50 A
10.00 A
60VTS Threshold I1 fault
50.00 A
15 V
60VTS Threshold V1
10.00 sec
60VTS Time Delay
OFF
60CTS Current Transformer
Supervision
7 V
60CTS Threshold V2
0.04 A
60CTS Threshold I2
0.20 A
10.00 sec
60CTS Time Delay
ON
Measurement Supervision
50 V
Voltage Threshold for
Balance Monitoring
0.75
Balance Factor for Voltage
Monitor
0.50 A
Current Threshold for
Balance Monitoring
2.50 A
0.50
Balance Factor for Current
Monitor
0.10 A
Summated Current Moni-
toring Threshold
0.50 A
0.10
Summated Current Moni-
toring Factor
ON
Fast Summated Current
Monitoring
Functions
241