Operating modes of the clock management
Operating mode
Internal
Pulse via binary input
Field bus (DNP)
NTP (IEC 61850)
GPS
IRIG-B
Setting Group Change Option of the Functional Settings
Number of available setting groups
The change can be performed via
IEC 61850 GOOSE (inter-device communication)
The GOOSE communication service of IEC 61850 is qualified for switchgear interlocking. Since the transmis-
sion time of GOOSE messages depends on both the number of IEC 61850 clients and the pickup condition of
the device, GOOSE is not generally qualified for protection-relevant applications. The protection application
must be checked with regard to the required transmission times and coordinated with the manufacturer.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Comments
Internal synchronization via RTC (default)
External synchronization with pulse via binary input
External synchronization via field bus
External synchronization using port F (IEC 61850)
External synchronization via GPS
External synchronization via IRIG-B
16 (parameter group A to P)
HMI at the device
DIGSI via user interface
Protocol using port F
Binary input
Technical Data
4.23 Additional Functions
575