Information List; En100-Module; Description - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr.
Parameter
6023
S3: x'
6024
S3: x'
6025
S3: Line angle
6026
S3: Line length
6027
S3: Line length

Information List

2.1.6.4
No.
Information
126
ProtON/OFF
356
>Manual Close
420
>Opened Ctrl 2
421
>Opened Ctrl 3
422
>Closed Ctrl 2
423
>Closed Ctrl 3
424
Open Ctrl 2
425
Close Ctrl 2
426
Open Ctrl 3
427
Close Ctrl 3
501
Relay PICKUP
511
Relay TRIP
533
Ia =
534
Ib =
535
Ic =
561
Man.Clos.Detect
2720
>Enable ANSI#-2
4601
>52-a
4602
>52-b
6011
>Opened Ctrl 1
6012
>Closed Ctrl 1
6013
Open Ctrl 1
6014
Close Ctrl 1
16019
>52 Wear start
16020
52 WearSet.fail
16027
52WL.blk I PErr
16028
52WL.blk n PErr

EN100-Module

2.1.7
2.1.7.1

Description

The EN100-Module enables integration of the 7SC80 in 100-Mbit communication networks in control and
automation systems with the protocols according to IEC 61850 standard. This standard permits uniform
communication of the devices without gateways and protocol converters. Even when installed in heteroge-
neous environments, SIPROTEC 4 relays therefore provide for open and interoperable operation. Parallel to the
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
Type of
Comments
Informa-
tion
IntSP
Protection ON/OFF (via system port)
SP
>Manual close signal
SP
>Opened Control device 2
SP
>Opened Control device 3
SP
>Closed Control device 2
SP
>Closed Control device 3
OUT
Open control device 2
OUT
Close control device 2
OUT
Open control device 3
OUT
Close control device 3
OUT
Relay PICKUP
OUT
Relay GENERAL TRIP command
VI
Primary fault current Ia
VI
Primary fault current Ib
VI
Primary fault current Ic
OUT
Manual close signal detected
SP
>Enable 50/67-(N)-2 (override 79 blk)
SP
>52-a contact (OPEN, if bkr is open)
SP
>52-b contact (OPEN, if bkr is closed)
SP
>Opened Control device 1
SP
>Closed Control device 1
OUT
Open control device 1
OUT
Close control device 1
SP
>52 Breaker Wear Start Criteria
OUT
52 Wear blocked by Time Setting Failure
OUT
52 Breaker Wear Logic blk Ir-CB>=Isc-CB
OUT
52 Breaker W.Log.blk SwCyc.Isc>=SwCyc.Ir
Default Setting
Comments
0.2420 Ω/mi
S3: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S3: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S3: Line angle
62.1 Miles
S3: Line length in miles
100.0 km
S3: Line length in kilometer
Functions
2.1 General
69