Settings

The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
1101
FullScaleVolt.
1102
FullScaleCurr.
1103
RE/RL
1104
XE/XL
1105
x'
1106
x'
1107
I MOTOR START
1108
P,Q sign
1109
Line angle
1110
Line length
1111
Line length
6001
S1: RE/RL
6002
S1: XE/XL
6003
S1: x'
6004
S1: x'
6005
S1: Line angle
6006
S1: Line length
6007
S1: Line length
6011
S2: RE/RL
6012
S2: XE/XL
6013
S2: x'
6014
S2: x'
6015
S2: Line angle
6016
S2: Line length
6017
S2: Line length
6021
S3: RE/RL
6022
S3: XE/XL
68
C
Setting Options
0.10 .. 800.00 kV
10 .. 50000 A
-0.33 .. 7.00
-0.33 .. 7.00
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
1A
0.40 .. 10.00 A
5A
2.00 .. 50.00 A
not reversed
reversed
10 .. 89 °
0.1 .. 1000.0 km
0.1 .. 650.0 Miles
-0.33 .. 7.00
-0.33 .. 7.00
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
-0.33 .. 7.00
-0.33 .. 7.00
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
-0.33 .. 7.00
-0.33 .. 7.00
Default Setting
Comments
20.00 kV
Measurem:FullScale-
Voltage(Equipm.rating)
400 A
Measurem:FullScaleCur-
rent(Equipm.rating)
1.00
Zero seq. compensating
factor RE/RL
1.00
Zero seq. compensating
factor XE/XL
0.2420 Ω/mi
feeder reactance per mile:
x'
0.0484 Ω/mi
0.1500 Ω/km
feeder reactance per km: x'
0.0300 Ω/km
2.50 A
Motor Start Current (Block
49, Start 48)
12.50 A
not reversed
P,Q operational measured
values sign
85 °
Line angle
100.0 km
Line length in kilometer
62.1 Miles
Line length in miles
1.00
S1: Zero seq. compen-
sating factor RE/RL
1.00
S1: Zero seq. compen-
sating factor XE/XL
0.2420 Ω/mi
S1: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S1: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S1: Line angle
62.1 Miles
S1: Line length in miles
100.0 km
S1: Line length in kilometer
1.00
S2: Zero seq. compen-
sating factor RE/RL
1.00
S2: Zero seq. compen-
sating factor XE/XL
0.2420 Ω/mi
S2: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S2: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S2: Line angle
62.1 Miles
S2: Line length in miles
100.0 km
S2: Line length in kilometer
1.00
S3: Zero seq. compen-
sating factor RE/RL
1.00
S3: Zero seq. compen-
sating factor XE/XL
SIPROTEC Compact, 7SC80, Manual